background image

18

www.fosterrefrigerator.com

Factory Reset

Where the controller was originally programmed by Foster and is dedicated to a specific appliance type it is possible to return the setting to they’re 
original programmed state.  If the controller was not programmed by Foster this function will return the parameters to the values in the original 
factory settings.

To reset the parameters:

 

- Press button 3 to activate the display

 

- Press button 1 to enter the user level menu

 

- Press button 2 until the display shows ‘rFp’

 

- Press button 3 once and ‘rFp’ will flash

 

- Press and hold button 3 for 3 seconds until the display shows ‘End’

The original parameters as described above have now been restored.
If at any point the sequence of button operations and display indications are not completed the controller will, after 30 seconds resume operation 
with no changes to the parameters having been made.

Defrost Indication

During defrost icon 4 will be illuminated.  The controller display will be determined by the value set in parameter ‘DDM’.

To start a defrost manually press and hold button 3 for 5 seconds.  This will turn off the appliance.  Continue to hold down button 3 after the 
appliance has turned off.  After a further 2 seconds the display will indicate a defrost has commenced (icon 4 illuminated) and the button can be 
released. While the defrost function is operating the display will be determined by the value set in parameter DDM.

The defrost function will operate until either the time set in parameter DTO or the temperature set in parameter DLI is reached.  Where parameter 
TE is set to NO defrost will function on a time basis only.  Upon completion of the defrost cycle the appliance will resume normal operation with 
the current temperature displayed.

Relay Test

The controller contains a relay test function to enable the service engineer to operate individual relays, or a combination of relays for diagnostic 
purposes.

To access the relay test:
 
 

- Place the controller in standby so that button 3 is pulsing

 

- Press button 3 once so that buttons 1, 2 and 4 are activated and flashing

 

- Press and hold buttons 2 and 4 for 5 seconds until the display shows ‘rLy’ and buttons 1 to 5 are all illuminated

The controller is now in relay test mode.

 

To activate relay 1 press button 1.  Icon 1 will illuminate.  To deactivate relay 1 press button 1 again and icon 1 will switch off.

 

To activate relay 2 press button 2.  Icon 3 will illuminate.  To deactivate relay 2 press button 2 again and icon 3 will switch off.

 

To activate relay 3 press button 4.  Icon 4 will illuminate.  To deactivate relay 3 press button 4 again and icon 4 will switch off.

 

To activate relay 4 press button 5.  Icon 8 will illuminate.  To deactivate relay 4 press button 5 again and icon 8 will switch off.

Multiple relays can be activated simultaneously to enable diagnostics.

Relay function:

 

Relay 1 - Red icon - Compressor

 

Relay 2 - Green icon - function determined by parameter SR1.  Evaporator Fan

 

Relay 3 - White icon - function determined by parameter SR2.  Where appliance has active defrost SR2 to will be set to DEF for defrost.

 

Relay 4 - Amber icon - function determined by parameter RL2.

To exit the relay test function press button 3 once.

Summary of Contents for ECORPO G3 EP1440G

Page 1: ...Service Manual EP700H EP700M EP700L EP700G EP700F EP700SH EP700SL EP700P EP1440H EP1440M EP1440L EP1440G EP700HH EP700HL EP700LL EP700H2 EP700L2 EP700LL Cabinets...

Page 2: ...your appliance Service Function Parameters Alarm Indicators Probe Data Relay Test Factory Reset Wiring Diagrams Maintenance Welcome to your interactive Foster service manual Here s how it works To re...

Page 3: ...ce should be located on a flat level surface correctly loaded Do not use mechanical devices to accelerate the defrost process Care should be taken not to damage the refrigeration circuit and or system...

Page 4: ...liance produces warm air when operating normally and requires adequate ventilation The dimensions indicated are a minimum As the operating temperature has been pre set no adjustments are required Allo...

Page 5: ...ernal temperature and button 3 Icon Button 1 Compressor running 1 Information menu 2 Keypad locked 2 Increase value 3 Evaporator fans running 3 Standby Exit Confirm 4 Defrost in progress 4 Decrease va...

Page 6: ...nd the shelf above Do not place product on the base of the appliance If it is required to store product on the base of the appliance please contact the Foster parts team to purchase the necessary shel...

Page 7: ...e If it is required to amend the value use buttons 2 and 4 followed by button 3 to save the new value User Level Parameters Mnemonic Description SP Appliance Set Point Loc Keypad Lock tA Actual air pr...

Page 8: ...DFT accumulated only in run mode FRO Do not use DoD Do not use TAD Do not use DFT Time interval between defrosts When this time has elapsed since the previous defrost in run mode a new defrost cycle i...

Page 9: ...essor stop FT2 Timed fan stop When FT2 0 the fans remain on all the time FT3 Timed fan run When FT3 0 and FT2 0 the fans remain OFF all the time ATM Alarm threshold management NON all temperature alar...

Page 10: ...ler R1 Do not use R1F Do not use R1 Do not use FAN Output enabled for evaporator fan switching FAN Do not use DEF Output enabled for defrost switching DEF Do not use ALO Contacts open when an alarm co...

Page 11: ...ed rate of change toward setpoint actual value away from setpoint mathematical algorithm applied A E the AVG weighted average between TAir T1 and TEvaporator T2 probes T3 TAuxiliary T3 probe value whe...

Page 12: ...60 60 0 0 0 0 0 CT1 4 4 4 4 5 5 4 4 5 4 4 5 5 4 5 4 4 5 CT2 7 6 6 7 5 5 7 6 5 6 7 5 5 6 5 6 6 5 PB 7 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 IT 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 1...

Page 13: ...0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 FT2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 FT3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ATM REL REL REL REL REL REL REL REL REL REL REL REL REL REL REL REL REL REL ALA 30 30 30 3...

Page 14: ...R DOR DOR NON NON DOR DOR DOR OS3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 D3A OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN OPN AHM NON NON NON NON NON NON NON NON NON NON NON NON NO...

Page 15: ...the bottom edge of the front cover If the cover is hinged up or removed for access purposes the door switch will not function and the door open alarm will be displayed tA Air probe has failed Call you...

Page 16: ...522 113 347 117 294 25 84 823 87 559 90 374 20 66 27 68 237 70 255 15 52 229 53 65 55 104 10 41 477 42 506 43 557 5 33 147 33 892 34 651 0 26 678 27 219 27 767 5 21 63 22 021 22 417 10 17 643 17 926...

Page 17: ...ve at all other times subject to the parameter FCM Door Switch The appliance is fitted with a magnetic door switch located in the underside of the front cover Where the door switch is open and followi...

Page 18: ...parameter DTO or the temperature set in parameter DLI is reached Where parameter TE is set to NO defrost will function on a time basis only Upon completion of the defrost cycle the appliance will resu...

Page 19: ...skets Door gaskets should be inspected periodically and cleaned where necessary with a warm damp cloth Do not use aggressive cleaning materials on the door gaskets Where door gaskets are damaged or no...

Page 20: ...20 www fosterrefrigerator com Wiring Diagrams EP700H Integral Condensing Unit...

Page 21: ...21 G3 Cabinets Service Manual EP700H Remote Condensing Unit...

Page 22: ...22 www fosterrefrigerator com EP700G Integral Condensing Unit...

Page 23: ...23 G3 Cabinets Service Manual EP700G Remote Condensing Unit...

Page 24: ...24 www fosterrefrigerator com EP700P Integral Condensing Unit...

Page 25: ...25 G3 Cabinets Service Manual EP700P Glass Door Integral Condensing Unit...

Page 26: ...26 www fosterrefrigerator com EP700F Integral Condensing Unit...

Page 27: ...27 G3 Cabinets Service Manual EP700F Remote Condensing Unit...

Page 28: ...28 www fosterrefrigerator com EP700M EP700L Integral Condensing Unit...

Page 29: ...29 G3 Cabinets Service Manual EP700M EP700L Remote Condensing Unit...

Page 30: ...30 www fosterrefrigerator com EP700HH Integral Condensing Unit...

Page 31: ...31 G3 Cabinets Service Manual EP700HH Remote Condensing Unit...

Page 32: ...32 www fosterrefrigerator com EP700HL Integral Condensing Unit...

Page 33: ...33 G3 Cabinets Service Manual EP700HL Remote Condensing Unit...

Page 34: ...34 www fosterrefrigerator com EP700LL Integral Condensing Unit...

Page 35: ...35 G3 Cabinets Service Manual EP700LL Remote Condensing Unit...

Page 36: ...36 www fosterrefrigerator com EP820HU Integral Condensing Unit...

Page 37: ...37 G3 Cabinets Service Manual EP1440H Integral Condensing Unit...

Page 38: ...38 www fosterrefrigerator com EP1440H Remote Condensing Unit...

Page 39: ...39 G3 Cabinets Service Manual EP1440G Integral Condensing Unit...

Page 40: ...40 www fosterrefrigerator com EP1440G Remote Condensing Unit...

Page 41: ...41 G3 Cabinets Service Manual EP1440M EP1440L Integral Condensing Unit...

Page 42: ...42 www fosterrefrigerator com EP1440M EP1440L Remote Condensing Unit...

Page 43: ...43 G3 Cabinets Service Manual...

Page 44: ...sterrefrigerator com Document ID code 00 570505 v1 By Appointment to Her Majesty Queen Elizabeth II Suppliers of Commercial Refrigeration Foster Refrigerator King s Lynn For service and spares For ser...

Reviews: