10
www.fosterrefrigerator.com
DAD
Delay before door open alarm
warning
CSD
‘Relay 1’ stop delay after door
open
‘0’ … ‘900’ - time in seconds (‘-1’ = ‘Relay’ does not de-energise / ‘0’ = instantaneous / ‘1’-
’900’ = de-energises after prescribed time elapses)
DOT
Door stop overide
If the door switch remains open for longer than ‘DOT’ minutes, the operating functionaity
returns to normal thermostatic control, howver the alarm will remain. When ‘DOT’ = ‘0’,
this function is disabled
DI1
‘DI1’ digital input
‘NON’ - Digital Input 1 not active
‘DOR’ - door input
‘ALR’ - when the input is activated (set by ‘D1A’) alarm ‘Alr’ alarm is generated, the
compressor is stopped and the defrosts are suspended
‘ECO’ - Do not use
‘RDS’ - Do not use
D1A ‘DI1’ activation
‘OPN’ - on open
‘CLS’ - on close
LCM
Light control mode
‘NON’ - light output not controlled
MAN’ - light output controlled through display operating button (when ‘SR1’, ‘SR2’ or ‘RL2’
= ‘LGT’ )
‘ECO’ - Do not use
‘DI1’ - Do not use
‘NI1’ - Do not use
‘DI2’ - Do not use
‘NI2’ - Do not use
SR1
SSR1 output operation
‘NON’ - Relay output disabled (always Off/Open)
‘LGT’ - Output enabled for light control
‘0-1’ - Relay contacts follow the on/standby state of controller
R1’ - Do not use
‘R1F’ - Do not use
‘-R1’ - Do not use
‘FAN’ - Output enabled for evaporator fan switching
‘-FAN’ Do not use
‘DEF’ - Output enabled for defrost switching
‘-DEF’ - Do not use
‘ALO’ - Contacts open when an alarm condition occurs
‘ALC’ - Contacts make when an alarm condition occurs
‘ACP’ - Do not use
‘AFH’ - Do not use
SR2 SSR2 output operation
Same operations and selection as ‘SR1’
RL2
RL2 output operation - same
operations and selection as
‘SR1’
Same operations and selection as ‘SR1’
ACN
Do not adjust
ACF
Do not adjust
AHS
Do not adjust
AHU
Do not adjust
AFT
Do not adjust
PMD
Do not adjust
MSV
Do not adjust
2CD
Do not adjust
SB
Stand-by button enabling
BOS
Button Operation Sounder
YES’ provides positive feedback (i.e. ‘beep’) every time a display button is pressed, ‘NO’
sounder is silenced during display button operation
RHC
Do not adjust
OSA Probe TAir (T1) offset
TE
Probe TEvaporator (T2)
enabling
OSE Probe TEvaporator (T2) offset
T3A
DI2 / TAuxiliary Probe Enabling
and Operation
‘NON’ - DI2 / Auxiliary probe not fitted
‘DSP’ - Auxiliary Probe - general purpose temperature measurement (i.e. stored product
temperature)
‘CND’ - Condenser probe - if measure temperature exceeds value of ‘AHT’ controller will
react as defined by ‘AHM’
‘2EU’ Do not use
‘DOR’ - Digital Input 2 used for door switch operation
‘ALR’ - Do not use
‘ECO’ - Do not use
‘RDS’ - Do not use
Summary of Contents for ECORPO G3 EP1440G
Page 20: ...20 www fosterrefrigerator com Wiring Diagrams EP700H Integral Condensing Unit...
Page 21: ...21 G3 Cabinets Service Manual EP700H Remote Condensing Unit...
Page 22: ...22 www fosterrefrigerator com EP700G Integral Condensing Unit...
Page 23: ...23 G3 Cabinets Service Manual EP700G Remote Condensing Unit...
Page 24: ...24 www fosterrefrigerator com EP700P Integral Condensing Unit...
Page 25: ...25 G3 Cabinets Service Manual EP700P Glass Door Integral Condensing Unit...
Page 26: ...26 www fosterrefrigerator com EP700F Integral Condensing Unit...
Page 27: ...27 G3 Cabinets Service Manual EP700F Remote Condensing Unit...
Page 28: ...28 www fosterrefrigerator com EP700M EP700L Integral Condensing Unit...
Page 29: ...29 G3 Cabinets Service Manual EP700M EP700L Remote Condensing Unit...
Page 30: ...30 www fosterrefrigerator com EP700HH Integral Condensing Unit...
Page 31: ...31 G3 Cabinets Service Manual EP700HH Remote Condensing Unit...
Page 32: ...32 www fosterrefrigerator com EP700HL Integral Condensing Unit...
Page 33: ...33 G3 Cabinets Service Manual EP700HL Remote Condensing Unit...
Page 34: ...34 www fosterrefrigerator com EP700LL Integral Condensing Unit...
Page 35: ...35 G3 Cabinets Service Manual EP700LL Remote Condensing Unit...
Page 36: ...36 www fosterrefrigerator com EP820HU Integral Condensing Unit...
Page 37: ...37 G3 Cabinets Service Manual EP1440H Integral Condensing Unit...
Page 38: ...38 www fosterrefrigerator com EP1440H Remote Condensing Unit...
Page 39: ...39 G3 Cabinets Service Manual EP1440G Integral Condensing Unit...
Page 40: ...40 www fosterrefrigerator com EP1440G Remote Condensing Unit...
Page 41: ...41 G3 Cabinets Service Manual EP1440M EP1440L Integral Condensing Unit...
Page 42: ...42 www fosterrefrigerator com EP1440M EP1440L Remote Condensing Unit...
Page 43: ...43 G3 Cabinets Service Manual...