22
Set Ups ID command: UPSID
Computer send: UPSID YYMMDDPPSSS <CR>
UPS reply : OK <CR>
Means: Ups product date < YY >/< MM >/< DD > (year/month/day), lot number < PP >
ranging from 01 to 31 and serial number < SSS > ranging from 000 to 511
Notes: “UPSID” is separated from “YYMMDDPPSSS” by two space key. And
Ups ID query command: Q7
Computer send: Q7< CR >
UPS reply : YYMMDDPPSSS V_xx<CR>
Means: Display the UPS ID YYMMDDPPSSS. The last 4 letters V_xx not more used now
DSP Firmware query command
Computer send: VERDSP< CR >
UPS reply: (VERDSP <NNNNN.NN><CR>
Means: Display version of DSP firmware.
MCU Firmware query command
Computer send: VERMR32< CR >
UPS reply: (VERMR32 <NNNNN.NN><CR>
Means: Display version of MCU firmware
Positive DC BUS (+BUS) voltage calibration command:
Computer send: BUSP+XX < CR > or BUSP-XX
UPS reply : : BUSP+XX or : BUSP-XX
Means: Increase average voltage of Positive Bus (+BUS), XX is two digits from 00 to 19, 1
represents about 0.5V.
Negative DC BUS (-BUS) voltage calibration command:
Computer send: BUSN+XX < CR > or BUSN-XX< CR >
UPS reply : BUSN+XX or : BUSN-XX
Means: Increase average voltage of Negative Bus (-BUS), XX is two digits from 00 to
19, .1 represents about 0.5V.
INV output voltage calibration command
Command Format: V+X < CR > or V-X < CR >
UPS reply: V+X or V-X
Means: Increase or decrease the inverter output voltage for calibration. X is single