(g) Load percentage before fault: LLL 

LLL is maximum of W% or VA%.    VA% is a percent of maximum VA. W% is a percent of 

maximum real power. 

(h) O/P current before fault: CCC 

CCC is a percent of maximum current. 

(i) Positive Bus voltage before fault: PPP 

P is an integer number ranging from 0 to 9. The unit is volt. 

(j) Negative Bus voltage before fault: NNN 

N is an integer number ranging from 0 to 9. The unit is volt. 

(k) Battery voltage before fault: BBB.B 

B is an integer number ranging from 0 to 9. The unit is volt   

(l) Temperature before fault: TT.T 

T is an integer number ranging from 0 to 9. The unit is degree in centigrade. 

(m) UPS running status before fault: <b7b6b5b4b3b2b1b0> 

<b7b6b5b4b3b2b1b0> is one byte of binary information. 
Each bit is transferred into ASCII code.   
<bn> is a binary number    “0” or “1”. 

Bit Remarks 
7 1:DCTODC 

on 

6 1:PFC 

on 

1: INVERTER on 

4 Reserved(always 

0) 

3 1:input 

relay 

on 

1:O/P relay on 

1 Reserved(always 

0) 

0 Reserved(always 

0) 

 
Example:  

Computer: QF<cr> 

UPS:    (04 208 41.0 160 50.0 102 100 160 190 041.0 69.0 01101100<cr> 

Means: Inverter fault in line mode 

I/P voltage is 208V. 

I/P frequency is 41.0HZ. 

O/P voltage is 160V. 

O/P frequency is 50.0HZ 

Load is 102% 

O/P current is 100% 

Positive Bus voltage is 160V 

Negative Bus voltage is 190V 

Battery voltage is 41.0V. 

Temperature is 69.0 

   

Battery SW off, PFC on , INVERTER on, input relay on , O/P relay on 

Summary of Contents for Elipse Series

Page 1: ...1 SERVICE MANUAL EL 6 10K Forza...

Page 2: ...6 The automatic UPS switch 10 4 2 7 The maintenance bypass switch 10 4 2 8 The battery switch 11 4 2 9 The battery charger 11 4 2 10 The controller 11 4 2 11 The auxiliary power supply 11 4 2 12 The v...

Page 3: ...t 37 5 4 2 Fault code definition and possible points 38 5 4 3 Quick Problem Identification process 41 5 4 4 Static Impedance Characteristic Of PCB board 42 5 5 COMPONENT LEVEL REPAIR 44 5 6 TEST AFTER...

Page 4: ...point of view please refer to section characteristic of the product Construction of the product how many pieces of PCB do the product make up please refer to construction of the product Functional blo...

Page 5: ...er service check all the wiring fasten all screws and connectors verify the polarity of batteries polarity of the DC BUS Cap have been correctly connected before applying power supply to the UPS and r...

Page 6: ...ians to repair and adjust a problematic UPS If the UPS still does not work properly please contact with us and we will be glad to help in solving any problems you met Because of the following unique f...

Page 7: ...over please follow steps and figures below STEP 1 Remove all the screws including those on the opposite side of the case refer to Figure 3 1 STEP 2 move the top cover and side cover upward as shown in...

Page 8: ...SCR O P EMI FILTER MB SW Controller Power Supply SPS Communication Interface Ventilation Chassis Figure 4 1 1 Functional block diagram The dashed indicates the interconnection of long backup time mod...

Page 9: ...ifier module rectifies the AC mains input into DC power of half waveform The rectifier remains in off state under battery mode 4 2 4 The voltage Booster module In line mode the voltage Booster boost t...

Page 10: ...the transfer between bypass and inverter output without any interruption zero transfer time 4 2 7 The maintenance bypass switch The Maintenance Bypass switch is a mechanical rotary switch In normal co...

Page 11: ...ontrols all of action of the UPS response and feedback to the query or action command of the communication interface Basically the controller includes the CPU Central Processing Unit which collects an...

Page 12: ...en the UPS and UPS The communication interface carries parallel operation control signal and common communication signal 4 2 12 The ventilation module To keep the UPS safely running the ventilation sy...

Page 13: ...ent hereafter is explanation of the PCB 4 3 1 Control Board Control board contains circuit implemented of the controller of the UPS Figure4 3 1 1 is a photo of the Control board Figure4 3 1 1 The Cont...

Page 14: ...provides comprehensive information of the UPS Figure 3 3 1 is a photo of a LED panel 4 3 4 O P EMI board I P EMI board O P EMI Board and I P EMI Board is the EMI filter local in input and output end o...

Page 15: ...gure 4 3 4 3 EL 10K s O P EMI 4 3 5 Charger Board Charger board contain the charger circuit Use for charging the bat Figure 4 3 5 2 Charger of standard model Figure 4 3 5 2Charger of long backup time...

Page 16: ...16 4 3 6 Parallel Board Parallel board is a dedicated board comprises parallel communication circuit Figure 3 6 Figure 4 3 6 3 Para board of 6 10K...

Page 17: ...ystem topology and wiring diagram For helping understand the electrical construction of the UPS system For more detail of the circuit and wiring connection of all PCB please refer to maintenance schem...

Page 18: ...18 Figure 4 5 EL6KS EL10KS UPS configuration diagram...

Page 19: ...al charge on the CAPs inside the UPS 4 A tool box include Wire cutters and clamps of different shape Cross screwdrivers Straight screw drivers sleeve spanner of difference diameter solder iron and sol...

Page 20: ...20 Configure the COM1 or COM2 properties as figure 5 2 1 1 b figure 5 2 1 1 b 1 Change the ASCII setup as figure 3 figure 5 2 1 1 C...

Page 21: ...yper terminal Normally after type a command the acknowledge of the UPS will be displayed on the next row For example UPSID setting command response with a OK on the next row represent action to set th...

Page 22: ...re MCU Firmware query command Computer send VERMR32 CR UPS reply VERMR32 NNNNN NN CR Means Display version of MCU firmware Positive DC BUS BUS voltage calibration command Computer send BUSP XX CR or B...

Page 23: ...alance 32 15 1C 10 11 Inverter Fault INV Soft Fail 8D 04 0B 42 52 OP short Fault 0F 0F 0F 0F Over Temp Fault 33 06 0A 43 53 Overload Fault 35 03 09 45 55 Bat SCR Short 0D 0D 0D 0D 0D Communication Fau...

Page 24: ...to 9 The unit is degree in centigrade m UPS running status before fault b7b6b5b4b3b2b1b0 b7b6b5b4b3b2b1b0 is one byte of binary information Each bit is transferred into ASCII code bn is a binary numb...

Page 25: ...mode automatically operation the panel to turn the UPS off to bypass before the turn the MBS 4 Switch off the mains input breaker on the rear panel of the UPS Disconnect battery input 5 Disassembly t...

Page 26: ...be saved into the memory of the UPS 14 To make sure the calibration has been saved you can turn on the UPS again and check the BUS voltage and Inverter output voltage once again 15 Switch off the main...

Page 27: ...each piece of battery should no sign of leakage of acid or deformation Voltage of each piece of battery should be checked if there is any piece has obvious voltage Difference 2V from the rest Recomme...

Page 28: ...arry out in an In depth inspection 5 3 1 3 PCB replacement For update or repair purpose PCB replacement needs to be carried out Hereafter is recommending procedure to replace a PCB 1 Stop all power su...

Page 29: ...rd can be referring to the procedure of replace a PCB stated in previous section 5 3 2 Parallel Maintenance Operation Recommending wiring of parallel operation system shown in figure 5 3 2 figure all...

Page 30: ...e UPS to maintenance bypass switch from UPS state to BPS state 7 Remain the mains input breaker on the rear panel of the UPS off Turn on the EXTERNAL input breaker of the UPS Check the output voltage...

Page 31: ...n on the UPSs and the system work in parallel operation 5 3 2 2 Operating procedure of adding a new UPS to the parallel system 1 Prepare the input and output cables the input output breaker switch and...

Page 32: ...value between JP1 and JP2 to check if the resistor is short circuit If the voltage difference is more than 1V the output relay of the UPS may have problem and can not be closed 16 Measure the voltage...

Page 33: ...rallel cables of the remained UPSs in parallel correctly connected to get most safety the parallel cable should be connect from a close ring in the parallel system after checking cable has been correc...

Page 34: ...S when the UPS parallel system is going to be in INV mode 3 Normally when maintenance bypass switch is open the UPS will transfer to bypass automatically and the maintenance bypass switch can be opera...

Page 35: ...but maybe highest cost b Board level Find out which PCB board get fail and replace the PCB board It will take medium time medium cost to finish the troubleshooting c Component level Find out which co...

Page 36: ...nd direction of finding the problem according the information got Section 5 4 1 provides a general guidance to selection the start point In most case from the fault warning code presented on the displ...

Page 37: ...the UPS Can the UPS be turned on Following instruction Test after repair Yes Yes Follow the display message explanation and solution table Start PCB board static checking process Yes Yes Check with p...

Page 38: ...onment over load or bad ventilation Make sure the ambient temperature should within the operation ranged and the ventilation should not be blocked Otherwise the there may be some hardware failure 1 6...

Page 39: ...eplace a parallel cable 3 Output power wiring of each UPS should be equal 1 3 4 5 6 Keep Beeping Error Model Model Pin configuration error the CPU does not recognize the configuration Ensure the model...

Page 40: ...v LED green LED Whenever the INV LED is turned on it shows that the loading current is supplied from utility power or battery via the inverter z Battery LED orange LED Whenever the battery LED is turn...

Page 41: ...41 5 4 3 Quick Problem Identification process Figure 5 4 3 1 Quick problem identification process...

Page 42: ...1 4M short 2 Q301 Q302 G K 10 short b Voltage boosting parts Item Checked components DVM Function Reference Value Fail Condition E C 800k short 1 Q306 Q308 Q310 Q307 Q309 Q311 G E 15 8k short or open...

Page 43: ...902 F903 F904 F905 F906 0 Open S D 1 7M Short 2 Q907 Q908 G S 32 Short or open 3 D901 D902 D903 DIODE 0 4V 0V A K 20M Short 4 Q909 G K 42 Short 5 4 4 3 Charger of long backup time model Item Checked c...

Page 44: ...e and connector right to place Please Note the label mark the designation of terminal connector the wire cable should be connected to 2 Check the Wiring again 3 Apply DC Power from power source with c...

Page 45: ...ower source 1 Make sure all power supply to the UPS remain off 2 Clip the voltage probe to the BUS N and BUS N for measurement of the DC BUS voltage 3 Set the DC power source current limiting threshol...

Page 46: ...apply 9 Endurance test 1 Apply battery of suitable capacity to the battery input of the UPS 2 Control the mains input to turn on off with timer control contactor or equivalent equipment 10s on 2s off...

Page 47: ...OUTPUT Output Waveform Pure Sinewave To AC Mode EFFICIENCY To Battery Mode 84 Battery Type Panasoinc 12V 7Ah Panasoinc 12V 9Ah Numbers of Batteries 20 pcs 20 pcs Backup Time Full Load 7min 5min Recha...

Page 48: ...kgs WEIGHT Rack Case kgs N A Operating Environment 0 40 C Relative Humidity 20 95 NON CONDENSING ENVIRONMENT Noise Level 55dB 1 meter Smart RS 232 Software supports Windows 98 NT 2000 XP 2003 ME Linux...

Page 49: ...The MODEL PORT JP01 of the second version 710 01902 02 or the later version CNTL board should be configured as follows Note 1 indicates that the jumper is connected 0 indicates that nothing is connec...

Page 50: ......

Page 51: ...51...

Reviews: