46
106346-06 - 8/19
FORCE
Installation, Operating & Service Manual
c. Allow the temperature to drop below control
setting. The burner must restart.
d. Boiler installation is not considered
complete until this check has been made.
5. CHECK LOW WATER CUT-OFF
a. Press and hold the test / settings button for
5 seconds.
b. The red low water light should illuminate
and the burner circuit (B1 & B2) should de-
energize.
6. CHECK AFTERMARKET LOW WATER CUT-
OFF CONTROL, if required on this boiler
application. See Appendix "B" at the rear of
this manual for 'How to Test'.
J . IF CONTROLS MEET REQUIREMENT
outlined
in Paragraph I.
Allow boiler to operate for approximately 30
minutes, confirm the boiler and system have no
leaks.
K .
IF CONTROLS DO NOT MEET
REQUIREMENTS
outlined in Paragraphs I-1
thru I-5, replace control and repeat checkout
procedures.
10
System Start-Up
(continued)