8
106346-06 - 8/19
FORCE
Installation, Operating & Service Manual
5. For minimum clearances to combustible
materials. See Figures 2A and 2B.
NOTICE:
Clearance to venting is for single wall
vent pipe. If Type L vent is used, clearance may
be reduced to the minimum required by the vent
pipe manufacturer.
C .
PROVIDE COMBUSTION AND VENTILATION
AIR .
Local and National Codes may apply and
should be referenced.
Boiler
Model
Beckett NX
Oil Burner
Part No.
Direct Vent
Conversion Kit
Part No.
FOVP Carton Part No.
FORCEOL140-E
106109-03
106401-01
100212-02 - 10 ft.
FORCEOL182-E
103369-01
100214-02 - 20 ft.
Figure 2B: Direct Vent - Minimum Installation Clearances To Combustible Materials (Inches)
NOTES
:
1. Listed clearances comply with American National
Standard ANSI/NFPA 31
,
Standard for the Installation of
Oil Burning Equipment.
2. FORCE OIL boilers can be installed in rooms with
clearances from combustible material as listed above.
Listed clearances cannot be reduced for alcove or closet
installations.
3. For reduced clearances to combustible material,
protection must be provided as described in the above
ANSI/NFPA 31 standard.
D . DIRECT VENT CONFIGURATIONS requires:
1. Beckett NX Burner
2. Direct Vent conversion Kit
3. Double Wall Flex Oil Vent Pipe (FOVP)
3"
3"
24"
6"
3"
3"
6"
6"
6"
VENT
PIPING
AIR INTAKE
PIPING
(REMOVED
FOR CLARITY)
FDVS
DIRECT
VENT
AIR
INTAKE
PIPING
AIR
INTAKE
PIPING
3"
2
Pre-Installation
(continued)
Table 2: Direct Vent Configuration Components
WARNING
Adequate combustion and ventilation air must
be provided to assure proper combustion and
to maintain safe ambient air temperatures.
Do not install boiler where gasoline or other
flammable vapors or liquids, or sources of
hydrocarbons (i.e. bleaches, fabric softeners,
etc.) are used or stored.
!