44
Instructions for the installer
Parameter
Settable values
Default values
Notes
P16 - TSP16
Ambient thermostat/remote control reading
delay
0 ÷ 199 sec.
0 sec.
-
P17 - TSP17
Anti-seize function timer
0 ÷ 30 sec.
10 sec.
-
P18 - TSP18
Anti-legionella function timer
0 ÷ 255 days
15 days
-
P19 - TSP19
Anti-legionella function temperature
35 ÷ 70 °C
65 °C
-
P20 - TSP20
Anti-legionella function operation timer
0 ÷ 255 minutes
30 minutes
-
P21 - TSP21
Association of supplementary input
0 ÷ 2
0
0 = no probe; 1 = ambient probe; 2 = external
probe
P22 - TSP22
Ambient probe triggering differential OFF
0.0 ÷ 1.0 °C
0.0 °C
resolution 0.1 (only with connected ambient
probe)
P23 - TSP23
Ambient probe triggering differential ON
-1.0 ÷ -0.1 °C
-0.5 °C
resolution 0.1 (only with connected ambient
probe)
P24 - TSP24
Ambient probe correction range
-5.0 ÷ 5.0 °C
0 °C
resolution 0.1 (only with connected ambient
probe)
P25 - TSP25
Type of modulation with connected ambient
probes
0 ÷ 1
1
0 = on/off; 1 = ambient probe modulation
P26 - TSP26
Flow temperature with P21=0 and P25=0
0 ÷ 78 °C
60 °C
only with connected ambient probe
P27 - TSP27
Heating timer reset temperature
20 ÷ 78 °C
40 °C
-
P28 - TSP28
Type of temperature visualization on display
0 ÷ 3
0
0 = flow temperature; 1 = ambient probe
temperature/external probe temperature; 2 =
return temperature; 3 = DHW temperature
P29
Circulation pump minimum speed
0 ÷ 100%
72%
-
P30
Circulation pump fixed speed
P29 ÷ 100%
100%
for all functions except heating
P31
Circulation pump speed in heating mode
P29 ÷ 101%
101%
With P31 = 101 automatic speed. With P31 <
101 speed fixed at the set value
P32
Flow/return differential in heating mode
0 ÷ 50 °C
30 °C
with P32 = 0, the return probe is disabled
P33
Circulation pump algorithm time base
0 ÷ 240 sec.
30 sec.
n.a.
Tab. 9 Limits to be set for TSP parameters and default values in relation to boiler type (TSP0) - II