35
Instructions for the installer
3.6.3
Air intake and flue gas venting via 80 mm split pipes
WARNING
The information given above is with reference to air intake/flue gas venting ducts made from smooth, rigid pipes approved and
supplied by the manufacturer.
Installation types C43 - C53 - C83
• Minimum permissible length of air intake pipe is 1 meter.
• Minimum permissible length of flue gas venting pipe is 1 meter.
• Maximum permissible length of intake/flue gas venting pipes is 95 meters (combined length of air intake and flue gas venting pipe).
• For each additional 1 meter of straight pipe maximum permissible length is to be reduced by 1 meter.
• For each additional 90° elbow, maximum permissible length is to be reduced by 1 meter.
• For each additional 45° elbow, maximum permissible length is to be reduced by 0.5 meter.
• The roof terminal reduces maximum permissible length by 5.5 meters.
• The wall terminal reduces maximum permissible length by 5.5 meters.
Fig. 12 Split pipe kit 0KITSDOP00
250
400
700
74
Ø 80
155
152,5
126
Fig. 13 Dimensions for split pipes
3.6.4
Air intake and flue gas venting via 60 mm split pipes
WARNING
The information given above is with reference to air intake/flue gas venting ducts made from smooth, rigid pipes approved and
supplied by the manufacturer.
Installation types C43 - C53 - C83
• Minimum permissible length of air intake pipe is 1 meter.
• Minimum permissible length of flue gas venting pipe is 1 meter.
• Maximum permissible length of air intake/flue gas discharge pipes is 24 meters (combined length of air intake and flue gas discharge pipe
length).
• For each additional 1 meter of straight pipe maximum permissible length is to be reduced by 1 meter.
• For each additional 90° elbow, maximum permissible length is to be reduced by 1 meter.
• For each additional 45° elbow, maximum permissible length is to be reduced by 0.5 meter.
• The wall terminal reduces maximum permissible length by 4 meters.