Operation Manual EMGZ490A
30.08.2019
20
In
de
x
Access M
ode
1)
Parameter
Instruction
Data
Type
Range
Data For
m
at
Uni
t
Description
0x23 R/W Scaling
Analogue
Output
unsigned
long
(unsigned
32 Bit)
0
to
200‘000‘000
#0.000 N
Determines
at
which force the
analog output
reaches its
maximal value of
10V
0x24 R/W Cut-off
frequency low
pass filter
feedback
(PROFINET)
unsigned
int
(unsigned
16 Bit)
1
to
2000
#0.0
Hz
Cut-off frequency
of PROFINET filter
0x25 R/W Cut-off
frequency low
pass filter
Analogue
output
unsigned
int
(unsigned
16 Bit)
1
to
2000
#0.0 Hz Cut-off
frequency
of analogue
output filter
0x30 W
Offset
compensation
-
-
-
-
Calculate offset
and store value
0x31 W
Calibration
signed
long
(signed 32
Bit)
±200‘000‘000 ±#0.00
0
N Calibrate
the
amplifier with
weight in N (must
correspond with
the used weight
for calibration).
1)
R = read, W = write, R/W = read and write.