AIR FOR COMBUSTION AND VENTILATION

Continued

4.  Compare the maximum Btu/Hr the space 

can support with the actual amount of Btu/

Hr used.

 

 _______ Btu/Hr (maximum the space can 

support)

 

 _______ Btu/Hr (actual amount of Btu/Hr 

used)

 

Example:

  63,360  Btu/Hr  (maximum  the 

space can support) 

 

 

79,000 Btu/Hr (actual amount of 

Btu/Hr used)

The space in the above example is a confined 

space because the actual Btu/Hr used is more 

than the maximum Btu/Hr the space can sup-

port. You must provide additional fresh air. Your 

options are as follows:

A.  Rework worksheet, adding the space of an 

adjoining room. If the extra space provides an 

unconfined space, remove door to adjoining 

room or add ventilation grills between rooms. 

See 

Ventilation Air  From  Inside  Building

page 8

.

B.  Vent room directly to the outdoors. See 

Ventilation Air From Outdoors

page 8.

C.  Install a lower Btu/Hr fireplace, if lower Btu/

Hr size makes room unconfined. 

If the actual Btu/Hr used is less than the 

maximum Btu/Hr the space can support,

 

the 

space is an unconfined space. You will need 

no additional fresh air ventilation.

 WARNING: If the area in which 

the heater may be operated does 

not meet the required volume for 

indoor combustion air, combus

-

tion and ventilation air shall be 

provided by one of the methods 

described in the 

National Fuel 

Gas Code, ANSI Z223.1/NFPA 54, 

the

 International Fuel Gas Code,

 

or applicable local codes.

  40,000
  39,000
  79,000

DETERMINING FRESH-AIR FLOW 

FOR HEATER LOCATION

Determining if You Have a Confined or 

Unconfined Space

Use this work sheet to determine if you have 

a confined or unconfined space.

Space:

 Includes the room in which you will 

install heater plus any adjoining rooms with 

doorless passageways or ventilation grills 

between the rooms.

1.  Determine the volume of the space (length 

x width x height).

 

Length x Width x Height =__________cu. ft. 

(volume of space)

 

Example: 

Space size 22 ft. (length) x 18 ft. 

(width) x 8 ft. (ceiling height) = 3168 cu. ft. 

(volume of space)

 

If additional ventilation to adjoining room 

is supplied with grills or openings, add the 

volume of these rooms to the total volume 

of the space. 

2.  Multiply the space volume by 20 to deter-

mine the maximum Btu/Hr the space can 

support.

 

 ________ (volume of space) x 20 = (Maxi-

mum Btu/Hr the space can support)

 

Example:

 3168 cu. ft. (volume of space) x 20 

= 63,360 (maximum Btu/Hr the space can 

support)

3.  Add the Btu/Hr of all fuel burning appliances 

in the space.

 

Vent-free fireplace 

 __________ Btu/Hr

 

Gas water heater* 

 __________ Btu/Hr

 

Gas furnace 

 __________ Btu/Hr

 

Vented gas heater 

 __________ Btu/Hr

 

Gas fireplace logs 

 __________ Btu/Hr

 

Other gas appl __________ Btu/Hr

 Total 

= _________ Btu/Hr

 

* Do not include direct-vent gas appliances. 

Direct-vent draws combustion air from the 

outdoors and vents to the outdoors.

 

Example:

 

Gas water heater 

 __________ Btu/Hr

 

Vent-free fireplace 

+

 _________ Btu/Hr

 Total 

= _________ Btu/Hr

Summary of Contents for VSGF28NTF

Page 1: ...Do not touch any electrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas suppli...

Page 2: ...xygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ven tilation section on page 6 of this manual This...

Page 3: ...tions if you cannot reach your gas supplier call the fire department SAFETY Continued DANGER Carbon monoxide poisoning may lead to death Carbon Monoxide Poisoning Early signs of carbon monoxide poison...

Page 4: ...all local codes In the absence of local codes use the latest edition of The National Fuel Gas Code ANSI Z223 1 NFPA 54 Available from American National Standards Institute Inc 1430 Broadway New York N...

Page 5: ...safety information 1 With utility knife cut carton all the way around above staples on bottom tray Lift carton off of heater Remove packing Note Hood is located in packing on right hand side of heater...

Page 6: ...entilation Unusually Tight Construction The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation However in buildings of un usually tight construction yo...

Page 7: ...theInternationalFuelGasCode or applicable local codes 40 000 39 000 79 000 DETERMINING FRESH AIR FLOW FOR HEATER LOCATION Determining if You Have a Confined or Unconfined Space Use this work sheet to...

Page 8: ...not provide openings for inlet or outlet air into attic if attic has a thermo stat controlled power vent Heated air entering the attic will activate the power vent Figure 4 Ventilation Air from Outdo...

Page 9: ...l If fireplace is not level log set will not work properly CHECK GAS TYPE Use the correct gas type natural or propane LP for your fireplace If your gas supply is not correct do not install fireplace C...

Page 10: ...3 1 2 from the wall This com bustible material must be 4 from the side of the fireplace opening see Figure 8 B Clearances from the top of the fireplace opening to the ceiling should not be less than...

Page 11: ...hammer or pliers 8 Place cardboard or other protective mate rial on top of hearth base Carefully set fireplace on protective material with back of fireplace inside mantel opening 9 If blower is insta...

Page 12: ...ce to Wall Studs Nailing Flanges Nails or Wood Screws 3 Install gas piping into fireplace location This installation includes an approved flexible gas line if allowed by local codes after the equipmen...

Page 13: ...CE Ifyourinstallationdoes not meet the minimum clear ances shown you must do one of the following raise the mantel to an accept able height remove the mantel NOTICE Surface temperatures of adjacent wa...

Page 14: ...dealer Minimum inlet pressure for purpose of input adjustment Figure 18 Gas Connection Sediment Trap Equipment Shutoff Valve With 1 8 NPT Tap 3 Minimum Cap Pipe Tee Nipple Joint Natural Gas From Gas M...

Page 15: ...replacing log base assembly Make sure the entire flexible gas line is in fireplace base area Reat tach log base assembly to fireplace with screws removed in step 2 WARNING Use pipe joint sealant that...

Page 16: ...f gas supply piping sys tem Apply noncorrosive leak detection fluid to all joints Bubbles forming show a leak 5 Correct all leaks at once 6 Reconnect fireplace and equipment shutoff valve to gas suppl...

Page 17: ...or failure to use only parts specifically approved with this heater may result in property damage or personal injury CAUTION Do not remove the data plates attached to the heater base assembly The data...

Page 18: ...gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or...

Page 19: ...s Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information page 18 If you don t smell gas go to the next step 5 Turn control knob counterclockwise to the PI...

Page 20: ...your fireplace could pro duce increased levels of carbon monoxide Followinstructionsat bottomofthispage Yellowflame on rear burner is normal NOTICE Do not mistake orange flames with yellow tipping Di...

Page 21: ...r store hardware store or home center may carry compressed air in a can If using compressed air in a can please follow the directions on the can If you don t follow directions on the can you could dam...

Page 22: ...ure Manifold 3 4 W C Inlet Gas Pressure in of water Maximum 10 5 W C Minimum 5 W C Shipping Weight 100 lbs For input adjustment Model VSGF28PTF Rating Variable 23 000 28 000 Btu Hr Type Gas Propane LP...

Page 23: ...ocated behind base panel 4 Replace ignitor cable 5 Replace piezo ignitor 6 Replace pilot assembly 7 Replace pilot assembly 1 Turn on gas supply or open equipment shutoff valve 2 Turn control knob to P...

Page 24: ...30 seconds 3 Fully open equipment shut off valve 4 A Contact local natural or propane LP gas company B Clean ODS pilot see Cleaning page 21 or re place ODS pilot assembly 5 Hand tighten until snug th...

Page 25: ...gas line checked by local natural or propane LP gas company 3 Observe minimum instal lation clearances see page 10 4 Clean burners see Clean ing page 21 or replace burner orifice s 1 Turn heater off...

Page 26: ...Clean ing page 21 1 Locate and correct all leaks see Checking Gas Con nections page 16 2 Replace control valve or gas control 1 Take apart gas tubing and remove foreign matter 2 Locate and correct al...

Page 27: ...ss listed on the back page of this manual FIREBOX BRICK LINER HFL300 Stacked Brick Pattern AgedAlmond HFL301 Stacked Brick Pattern Aged Red HFL310 Herringbone Brick Pattern Aged Almond HFL311 Herringb...

Page 28: ...www fmiproducts com 119303 01G 28 11 13 23 17 9 4 6 10 18 7 8 27 1a 1b 1f 1c 1d 1e 15 3 2 19 22 20 16 21 12 12 24 18 25 14 26 5 PARTS MODELS VSGF28NTF AND VSGF28PTF...

Page 29: ...1 10 098271 10 Ignitor Cable 1 11 Firebox Bottom 1 12 098867 10 Gas Regulator 1 098867 09 Gas Regulator 1 13 101004 01 Front Burner Injector 1 101004 04 Front Burner Injector 1 14 102845 01 Inlet Tub...

Page 30: ...www fmiproducts com 119303 01G 30 PARTS MODELS VSGF28NTF AND VSGF28PTF 1 2 3 4 16 16 6 12 18 10 10 7 13 16 26 24 16 23 25 20 24 24 21 16 16 27 17 14 5 16 16 15 8 9 19 22 11 11 11...

Page 31: ...ox Support 2 11 099230 01 Shoulder Screw 4 12 101872 03 Firebox Top 1 13 101346 01 Outer Base 1 14 Firebox Wrapper 1 15 101614 02 Limit Switch Thermal Disk Assembly 1 16 M11084 26 Hex Screw 10 57 17 0...

Page 32: ...s product and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic ma...

Reviews: