background image

www.fmiproducts.com

56131L

19

Venting with Two 90° Elbows

 Vertical (V)  Horizontal (H

1

) + 

 

 

Horizontal (H

2

)

  5' min. 

2' max.

  6' min. 

4' max.

  7' min. 

6' max.

  8' min. 

8' max.

  20' max. 

8' max.

Figure 29 - Vertical Rigid Venting 

Configuration Using Two 90° Elbows 

with Two Horizontal Runs

Venting with One 90° Elbow

  Vertical (V)  Horizontal (H)

 

5' min. 

2' max.

 

6' min. 

4' max.

 

7' min. 

6' max.

 

8' min. 

8' max.

 

20' max. 

8' max.

Figure 30 - Vertical Rigid Venting 

Configuration Using One 90° Elbow

VENTING INSTALLATION

Continued

Vertical Termination Configurations

Figures 29 through 32 show four different 

configurations for vertical termination. These 

minimum vertical rises are based on horizon

-

tal runs with a minimum of 1/4" upwards pitch 

per foot and do not reflect constraints on a 

vertical system with 45° or greater offset.

45° Starter Elbow

Note: Install restrictor 

into inner collar of 

fireplace as shown.

45° Starter Elbow

Note: Install restrictor 

into inner collar of 

fireplace as shown.

Figure 27 - Cathedral Ceiling Support 

Box Installation

Cut hole 1/8"  

larger than  

support box when 

projected onto roofline

2" minimum below 

finished ceiling

Cathedral 

ceiling 

support box

Level

Cathedral Ceiling Installation

1.  Remove shingles or other roof covering as 

necessary to cut rectangular hole for sup-

port box. Mark outline of cathedral ceiling 

support box on roof sheathing using the 

locating hole as a center point.

2.  Cut hole 1/8" larger than the support box 

outline (see Figure 27).

3.  Lower support box through hole in roof 

until bottom of box extends at least 2" 

below ceiling (see Figure 27). Align sup

-

port box vertically and horizontally using 

a level. Temporarily tack support box in 

place through inside walls and into roof 

sheathing.

4.  Using tin snips, cut support box from top 

corners down to roofline and fold result

-

ing flaps over roof sheathing (see Figure 

28). Apply a bead of non-hardening mas

-

tic around top edges of support box to 

make a seal between box and roof. Nail 

in place with roofing nails. Remove any 

combustible material that might be inside 

of support box.

5.  Complete cathedral ceiling installation by 

following the same procedures outlined in 

steps 2 through 7 for 

Flat Ceiling Installa-

tion, 

page 18

.

Non-hardening 

Mastic under all 

edges of support 

box before nailing

Figure 28 - Installed Cathedral Ceiling 

Support Box

Summary of Contents for Peninsula VDVF36

Page 1: ...ch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Insta...

Page 2: ...ces State of Massachusetts The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts WARNING Thisproductcon tainsand orgenerateschemicals known to the Stat...

Page 3: ...and proper operation of this fireplace WARNING Any change to this fireplace or it s controls can be dangerous Do not modify this fireplace under any circum stances Any parts removed for servicingmust...

Page 4: ...ic and away from furniture and draperies Do not place clothing or other flammable material on or near the appliance Never place any objects on the appliance Do not use this fireplace to cook food or b...

Page 5: ...y tank s inside any structure Locate propane LP supply tank s outdoors To prevent performance problems do not use propane LP fuel tank of less than 100 lbs capacity 2 If you smell gas shut off gas sup...

Page 6: ...2 5 8 34 3 4 3 BACK VIEW TOP VIEW Left Side Right Side Front Back 24 1115 16 101 2 11 2 11 2 101 2 FRONT VIEW 30 Opening 24 25 RIGHT SIDE 22 5 8 43 1 8 32 Opening 1 7 8 1 7 8 BACK VIEW 39 3 4 26 3 8 3...

Page 7: ...REMENTS Determine the safest and most efficient loca tion for your FMI PRODUCTS LLC direct vent fireplace Make sure that rafters and wall studs are not in the way of the venting system Choose a locati...

Page 8: ...Figure 5 Minimum Clearances See Thru Shown Combustible Material Drywall 2 x 4 Stud Minimum 1 Clearance from Side Only for See Thru FRAMING Once final location has been determined observing clearances...

Page 9: ...n 10 Square Min Figure 12 Rough Opening for Installing Exterior Vent Terminal Vertical Height Depends on Installation 26 3 8 Horizontal Length Depends on Installation 90o Elbow 45o Elbow Figure 13 Ven...

Page 10: ...1 also known as NFPA 54 These models are approved for use with FMI PRODUCTS LLC 5 8 Series rigid type direct vent pipe as supplied by FMI PROD UCTS LLC or with approved types of flexible vent pipe no...

Page 11: ...US if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m horizontally L...

Page 12: ...ly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than 1 2 in size GAS VENT DIRECTLY BELOW KEEP...

Page 13: ...uired You may use a chase with a vent termination with exposed pipe on exterior of house See Installing Vent System in a Chase page 14 Your FMI PRODUCTS LLC direct vent fireplace has been tested for a...

Page 14: ...stallation for Horizontal Termination The maximum vertical run is 30 see Installation for Vertical Termination page 17 Installing Vent System in a Chase A chase is a vertical box like structure built...

Page 15: ...re terminals are available one for rigid pipe applications and one for flex pipe ap plications A round vent termination with a slip fit connection is also provided for rigid pipe applications to be us...

Page 16: ...ate number of spring spacers at ends and closest bend to termination to prevent kinks or collapsing on the fire Do not use screws with flex pipe Vent system must be code inspected and released before...

Page 17: ...Vent H Min Height from Roof Figure 25 Vertical Vent Termination Clearance ROOF PITCH H Min Flat to 6 12 1 0 6 12 to 7 12 1 25 Over 7 12 to 8 12 1 5 Over 8 12 to 9 12 2 0 Over 9 12 to 10 12 2 5 Over 1...

Page 18: ...ctions you must support vent pipe every 3 feet Use wall straps for this purpose see Figure 24 page 17 When ever possible use 45 elbows instead of 90 elbows The 45 elbow offers less restriction to the...

Page 19: ...to roofline 2 minimum below finished ceiling Cathedral ceiling support box Level Cathedral Ceiling Installation 1 Remove shingles or other roof covering as necessary to cut rectangular hole for sup po...

Page 20: ...Configuration With No Horizontal Run Vertical Venting V 40 max Figure 33 Recommended 12 Extension for High Altitude Installation 45 Starter Elbow Note Install restrictor into inner collar of fireplac...

Page 21: ...58 Basement Vent Kit Galvanized Includes 45 Elbow 7 12 Adjustable Pipe Wall Firestop Horizontal Square Termination 4 Pipe 90 Elbow 20 Screws VKS 58 Snorkel Vent Kit Galvanized Includes 45 Elbow 7 12 A...

Page 22: ...e and is located on the lower right side of appliance see Figure 37 page 23 The variable speed controller is mounted on a magnetic base and may be positioned anywhere within an accessible distance beh...

Page 23: ...ver SKYTECH Model Optional Fan Kit Plug Receiver Pull to Remove Insulation Tab Battery Cover 12 Volt Battery Figure 40 Installing Battery in Hand Held Remote Control Unit SKYTECH Figure 37 Connecting...

Page 24: ...rom the gas supply piping system by closing its individual equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa...

Page 25: ...T S T E A a n d V DVF36TPNPEA TSTPEA models see Fig ure 44 O F F P I L O T ON L O HI P ILOT E A 16AI 7 TPTH TP TH Figure 43 Millivolt Control Valve Pilot Adjustment Cap ON OFF Knob Outlet Pressure Inl...

Page 26: ...top of logs B a shown in Figure 50 11 When finished installing logs close glass door Make certain safety door switch is fully pressed by door frame before secur ing four 4 spring loaded latches 12 Re...

Page 27: ...proper clearances are observed see Clearances page 7 IMPORTANT Louvered openings must not be obstructed and upper and lower panels must remain removable for FIREPLACE INSTALLATION Continued servicing...

Page 28: ...f burner and pilot as sembly In cleaning take care not to alter pilot or burner location Be sure appliance is cool before each maintenance session CAUTION Theapplianceand logs can get very hot Handle...

Page 29: ...move glass from frame Use any glass cleaner to clean glass Do not use abrasive clean ers as this may damage glass 3 If replacement is necessary entire assem bly frame and glass must be replaced If gla...

Page 30: ...S TO APPLIANCE 1 Turn off wall switch 2 Turn off all electric power to appliance if service is to be performed 3 Remove control access panel 4 Push in gas control knob slightly and turn clockwise to O...

Page 31: ...ian or gas supplier OPERATION Continued SPECIFICATIONS V DVF36TPNA A HA V DVF36TSTA A HA Input Rating 35 000 23 300 Btu Hr Fuel Natural Gas Manifold Pressure 3 5 W C Minimum Supply Pressure 4 5 W C Ma...

Page 32: ...technician replace pilot line 7 Replace control valve see Replacement Parts and Ac cessories page 35 8 Tighten thermocouple or replace 1 Check wiring connection Refer to Wiring Diagrams page 34 1 Chec...

Page 33: ...hoses Con sult pipe fitter or plumber 2 Repeat lighting procedure several times to purge air from lines If unit will still not light contact a qualified ser vice and repair technician 3 Remove debris...

Page 34: ...nd valve are set to ON position Frequent main burner outage WIRING DIAGRAMS GND J BOX RECEPTACLE GRN BLK WHT GRN NOT SUPPLIED INCOMING 120V AC FUSE BOX OR BREAKER FIELD WIRE WHT BLK CONNECTORS Variabl...

Page 35: ...at 1 866 328 4537 When calling please have your model and serial numbers of your fireplace ready You can also visit our web site at www fmiproducts com REPLACEMENT PARTS Contact authorized dealers of...

Page 36: ...ivolt Wires Wall Switch and Cover Plate BLOWER KIT DVFFBK For all models Increases air circulation to maximize heat distribution PARTS AND ACCESSORIES ON OFF MANUAL GAS CONTROL VALVE Natural 14389 Pro...

Page 37: ...ront Bottom 25854 Left Right Bottom 25856 Rear 25855 Front Bottom Left Right Bottom Rear For Peninsula and See Thru PIEZO IGNITOR 097159 04 GRATE 11184 PARTS AND ACCESSORIES Continued BURNER ASSEMBLY...

Page 38: ...____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______...

Page 39: ...____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______...

Page 40: ...will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic material labor and incidental costs asso...

Reviews: