background image

www.fmiproducts.com

56131L

12

REQUIREMENTS FOR THE COMMONWEALTH OF 

MASSACHUSETTS

For all side wall horizontally vented gas fueled 

equipment installed in every dwelling, building or 

structure used in whole or in part for residential 

purposes, including those owned or operated by 

the Commonwealth and where the side wall ex-

haust vent termination is less than seven (7) feet 

above finished grade in the area of the venting, 

including but not limited to decks and porches, 

the following requirements shall be satisfied:

INSTALLATION OF CARBON 

MONOXIDE DETECTORS

At the time of installation of the side wall horizon

-

tal vented gas fueled equipment, the installing 

plumber or gasfitter shall observe that a hard 

wired carbon monoxide detector with an alarm 

and battery backup is installed on the floor level 

where the gas equipment is to be installed. In 

addition, the installing plumber or gasfitter shall 

observe that a battery operated or hard wired car-

bon monoxide detector with an alarm is installed 

on each additional level of the dwelling, building or 

structure served by the side wall horizontal vented 

gas fueled equipment. It shall be the responsibility 

of the property owner to secure the services of 

qualified licensed professionals for the installation 

of hard wired carbon monoxide detectors.

In  the  event  that  the  side  wall  horizontally 

vented gas fueled equipment is installed 

in a crawl space or an attic, the hard wired 

carbon monoxide detector with alarm and 

battery back-up may be installed on the next 

adjacent floor level.

In the event that the requirements of this 

subdivision can not be met at the time of 

completion of installation, the owner shall 

have a period of thirty (30) days to comply with 

the above requirements; provided, however, 

that during said thirty (30) day period, a battery 

operated carbon monoxide detector with an 

alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required 

in accordance with the above provisions shall 

comply with NFPA 720 and be ANSI/UL 2034 

listed and IAS certified.

SIGNAGE

A metal or plastic identification plate shall be 

permanently mounted to the exterior of the 

building at a minimum height of eight (8) feet 

above grade directly in line with the exhaust 

vent terminal for the horizontally vented gas 

fueled heating appliance or equipment. The 

sign shall read, in print size no less than 1/2" in 

size, "GAS VENT DIRECTLY BELOW. KEEP 

CLEAR OF ALL OBSTRUCTIONS".

INSPECTION

The state or local gas inspector of the side 

wall horizontally vented gas fueled equipment 

shall not approve the installation unless, upon 

inspection, the inspector observes carbon 

monoxide detectors and signage installed in 

accordance with the provisions of 248 CMR 

5.08(2)(a) 1 through 4.

EXEMPTIONS: The  following  equipment  is 

exempt from 248 CMR 5.08(2)(a) 1 through 4:

•  The equipment listed in Chapter 10 entitled 

"Equipment Not Required To Be Vented" 

in the most current edition of NFPA 54 as 

adopted by the Board; and

•  Product Approved  side  wall  horizontally 

vented gas fueled equipment installed in a 

room or structure separate from the dwell-

ing, building or structure used in whole or 

in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided 

When the manufacturer of Product Approved 

side wall horizontally vented gas equipment 

provides a venting system design or venting 

system components with the equipment, the 

instructions provided by the manufacturer for 

installation of the equipment and the venting 

system shall include:

•  Detailed instructions for the installation of 

the venting system design or the venting 

system components; and

•  A complete parts list for the venting system 

design or venting system.

Gas Equipment Venting System Not 

Provided

When the manufacturer of a Product Ap-

proved side wall horizontally vented gas fu

-

eled equipment does not provide the parts for 

venting the flue gases, but identifies "special 

venting systems", the following requirements 

shall be satisfied by the manufacturer:

• 

The referenced "special venting system" in-

structions shall be included with the appliance 

or equipment installation instructions; and

•  The "special venting systems" shall be Prod

-

uct Approved by the Board, and the instruc-

tions for that system shall include a parts list 

and detailed installation instructions.

A copy of all installation instructions for all 

Product Approved  side  wall  horizontally 

vented gas fueled equipment, all venting in-

structions, all parts lists for venting instruc-

tions, and/or all venting design instructions 

shall remain with the appliance or equipment 

at the completion of the installation.

Summary of Contents for Peninsula VDVF36

Page 1: ...ch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Insta...

Page 2: ...ces State of Massachusetts The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts WARNING Thisproductcon tainsand orgenerateschemicals known to the Stat...

Page 3: ...and proper operation of this fireplace WARNING Any change to this fireplace or it s controls can be dangerous Do not modify this fireplace under any circum stances Any parts removed for servicingmust...

Page 4: ...ic and away from furniture and draperies Do not place clothing or other flammable material on or near the appliance Never place any objects on the appliance Do not use this fireplace to cook food or b...

Page 5: ...y tank s inside any structure Locate propane LP supply tank s outdoors To prevent performance problems do not use propane LP fuel tank of less than 100 lbs capacity 2 If you smell gas shut off gas sup...

Page 6: ...2 5 8 34 3 4 3 BACK VIEW TOP VIEW Left Side Right Side Front Back 24 1115 16 101 2 11 2 11 2 101 2 FRONT VIEW 30 Opening 24 25 RIGHT SIDE 22 5 8 43 1 8 32 Opening 1 7 8 1 7 8 BACK VIEW 39 3 4 26 3 8 3...

Page 7: ...REMENTS Determine the safest and most efficient loca tion for your FMI PRODUCTS LLC direct vent fireplace Make sure that rafters and wall studs are not in the way of the venting system Choose a locati...

Page 8: ...Figure 5 Minimum Clearances See Thru Shown Combustible Material Drywall 2 x 4 Stud Minimum 1 Clearance from Side Only for See Thru FRAMING Once final location has been determined observing clearances...

Page 9: ...n 10 Square Min Figure 12 Rough Opening for Installing Exterior Vent Terminal Vertical Height Depends on Installation 26 3 8 Horizontal Length Depends on Installation 90o Elbow 45o Elbow Figure 13 Ven...

Page 10: ...1 also known as NFPA 54 These models are approved for use with FMI PRODUCTS LLC 5 8 Series rigid type direct vent pipe as supplied by FMI PROD UCTS LLC or with approved types of flexible vent pipe no...

Page 11: ...US if greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m horizontally L...

Page 12: ...ly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than 1 2 in size GAS VENT DIRECTLY BELOW KEEP...

Page 13: ...uired You may use a chase with a vent termination with exposed pipe on exterior of house See Installing Vent System in a Chase page 14 Your FMI PRODUCTS LLC direct vent fireplace has been tested for a...

Page 14: ...stallation for Horizontal Termination The maximum vertical run is 30 see Installation for Vertical Termination page 17 Installing Vent System in a Chase A chase is a vertical box like structure built...

Page 15: ...re terminals are available one for rigid pipe applications and one for flex pipe ap plications A round vent termination with a slip fit connection is also provided for rigid pipe applications to be us...

Page 16: ...ate number of spring spacers at ends and closest bend to termination to prevent kinks or collapsing on the fire Do not use screws with flex pipe Vent system must be code inspected and released before...

Page 17: ...Vent H Min Height from Roof Figure 25 Vertical Vent Termination Clearance ROOF PITCH H Min Flat to 6 12 1 0 6 12 to 7 12 1 25 Over 7 12 to 8 12 1 5 Over 8 12 to 9 12 2 0 Over 9 12 to 10 12 2 5 Over 1...

Page 18: ...ctions you must support vent pipe every 3 feet Use wall straps for this purpose see Figure 24 page 17 When ever possible use 45 elbows instead of 90 elbows The 45 elbow offers less restriction to the...

Page 19: ...to roofline 2 minimum below finished ceiling Cathedral ceiling support box Level Cathedral Ceiling Installation 1 Remove shingles or other roof covering as necessary to cut rectangular hole for sup po...

Page 20: ...Configuration With No Horizontal Run Vertical Venting V 40 max Figure 33 Recommended 12 Extension for High Altitude Installation 45 Starter Elbow Note Install restrictor into inner collar of fireplac...

Page 21: ...58 Basement Vent Kit Galvanized Includes 45 Elbow 7 12 Adjustable Pipe Wall Firestop Horizontal Square Termination 4 Pipe 90 Elbow 20 Screws VKS 58 Snorkel Vent Kit Galvanized Includes 45 Elbow 7 12 A...

Page 22: ...e and is located on the lower right side of appliance see Figure 37 page 23 The variable speed controller is mounted on a magnetic base and may be positioned anywhere within an accessible distance beh...

Page 23: ...ver SKYTECH Model Optional Fan Kit Plug Receiver Pull to Remove Insulation Tab Battery Cover 12 Volt Battery Figure 40 Installing Battery in Hand Held Remote Control Unit SKYTECH Figure 37 Connecting...

Page 24: ...rom the gas supply piping system by closing its individual equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa...

Page 25: ...T S T E A a n d V DVF36TPNPEA TSTPEA models see Fig ure 44 O F F P I L O T ON L O HI P ILOT E A 16AI 7 TPTH TP TH Figure 43 Millivolt Control Valve Pilot Adjustment Cap ON OFF Knob Outlet Pressure Inl...

Page 26: ...top of logs B a shown in Figure 50 11 When finished installing logs close glass door Make certain safety door switch is fully pressed by door frame before secur ing four 4 spring loaded latches 12 Re...

Page 27: ...proper clearances are observed see Clearances page 7 IMPORTANT Louvered openings must not be obstructed and upper and lower panels must remain removable for FIREPLACE INSTALLATION Continued servicing...

Page 28: ...f burner and pilot as sembly In cleaning take care not to alter pilot or burner location Be sure appliance is cool before each maintenance session CAUTION Theapplianceand logs can get very hot Handle...

Page 29: ...move glass from frame Use any glass cleaner to clean glass Do not use abrasive clean ers as this may damage glass 3 If replacement is necessary entire assem bly frame and glass must be replaced If gla...

Page 30: ...S TO APPLIANCE 1 Turn off wall switch 2 Turn off all electric power to appliance if service is to be performed 3 Remove control access panel 4 Push in gas control knob slightly and turn clockwise to O...

Page 31: ...ian or gas supplier OPERATION Continued SPECIFICATIONS V DVF36TPNA A HA V DVF36TSTA A HA Input Rating 35 000 23 300 Btu Hr Fuel Natural Gas Manifold Pressure 3 5 W C Minimum Supply Pressure 4 5 W C Ma...

Page 32: ...technician replace pilot line 7 Replace control valve see Replacement Parts and Ac cessories page 35 8 Tighten thermocouple or replace 1 Check wiring connection Refer to Wiring Diagrams page 34 1 Chec...

Page 33: ...hoses Con sult pipe fitter or plumber 2 Repeat lighting procedure several times to purge air from lines If unit will still not light contact a qualified ser vice and repair technician 3 Remove debris...

Page 34: ...nd valve are set to ON position Frequent main burner outage WIRING DIAGRAMS GND J BOX RECEPTACLE GRN BLK WHT GRN NOT SUPPLIED INCOMING 120V AC FUSE BOX OR BREAKER FIELD WIRE WHT BLK CONNECTORS Variabl...

Page 35: ...at 1 866 328 4537 When calling please have your model and serial numbers of your fireplace ready You can also visit our web site at www fmiproducts com REPLACEMENT PARTS Contact authorized dealers of...

Page 36: ...ivolt Wires Wall Switch and Cover Plate BLOWER KIT DVFFBK For all models Increases air circulation to maximize heat distribution PARTS AND ACCESSORIES ON OFF MANUAL GAS CONTROL VALVE Natural 14389 Pro...

Page 37: ...ront Bottom 25854 Left Right Bottom 25856 Rear 25855 Front Bottom Left Right Bottom Rear For Peninsula and See Thru PIEZO IGNITOR 097159 04 GRATE 11184 PARTS AND ACCESSORIES Continued BURNER ASSEMBLY...

Page 38: ...____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______...

Page 39: ...____________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______...

Page 40: ...will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic material labor and incidental costs asso...

Reviews: