INSTALLATION
Continued
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required
clearances between fireplace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between
mantel shelf and top of fireplace opening, a
hood is not required (see Figure 6).
Figure 6 - Minimum Mantel Clearances
Without Using Hood
14"
Min.
Combustible
Material
Noncombustible Material
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Figure 7 - Minimum Mantel Clearances
When Using Hood
Minimum Non-
Combustible
Material
Minimum Non-
Combustible
Material Height
Distances to
Underside of
Mantel
Top of Fireplace
Opening
Underside of
Mantel Shelf
12"
(A)
18"
20"
22"
24"
All minimum
distances are
in inches
2
1/2
"
6"
8"
10"
Mantel Shelf
Minimum
Noncombustible
Material
8"
Min.
12"
15" 18" 20"
2
1/2
"
6"
8"
10"
12"
Distances to
Underside of
Mantel
Hood (GA6050
or GA6053)
Top of
Fireplace
Opening
Underside
of Mantel
Shelf
Mantel Shelf
Hearth
5"
Min.
Combustible
Material
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
NOTICE: Surface temperatures
of adjacent walls and mantels be
-
come hot during operation. Walls
and mantels above the firebox
may become hot to the touch.
If installed properly, these tem
-
peratures meet the requirement
of the national product standard.
Follow all minimum clearances
shown in this manual.
NOTICE: If your installation does
not meet the minimum clear-
ances shown, you must do one
of the following:
• operate the logs only with the
flue damper open
• raise the mantel to an accept
-
able height
• remove the mantel
FLOOR CLEARANCES
A. If installing appliance on the floor level,
you must maintain the minimum distance
of 14" to combustibles (see Figure 8).
B. If combustible materials are less than 14"
to the fireplace, you must install appliance
at least 5" above the combustible flooring
(see Figure 9).
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6, are not
met, you must have a hood. When using a
hood there are still certain minimum mantel
clearances required. Follow minimum clear-
ances shown in Figure 7, when using hood.