LOG SIZING REQUIREMENTS
Log
Size
Minimum Firebox Size
Height Depth
Front
Width
Rear*
Width
18"
17"
13.5"
20"
14"
24"
17"
13.5"
26"
18"
30"
21"
13.5"
32"
22"
36"
21"
13.5"
38"
27
1
/
2
"
*Measured at 13.5" depth
CAUTION: This heater cre-
ates warm air currents. These
currents move heat to wall sur-
faces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities (such as, but
not limited to, tobacco smoke,
aromatic candles, cleaning flu-
ids, oil or kerosene lamps, etc.) in
the air exist, may discolor walls
or cause odors.
IMPORTANT:
Vent-free heaters add moisture
to the air. Although this is beneficial, installing
heater in rooms without enough ventilation
air may cause mildew to form from too much
moisture. See
Air for Combustion and Ventila-
tion
, page 6.
CHECK GAS TYPE
Use the correct type of gas (natural or
propane/LP). If your gas supply is not the
correct gas type, do not install heater. Call
dealer where you bought heater for proper
type heater.
WARNING: This appliance
is for either natural gas or pro-
pane/LP gas but not both. Gas
type is indicated on the rating
plate Field conversion is not
permitted.
INSTALLATION AND CLEARANCES
FOR VENT-FREE OPERATION
WARNING: Maintain the
minimum clearances. If you
can, provide greater clearances
from floor, ceiling and adjoining
wall.
INSTALLATION
Continued
Carefully follow the instructions below. This
will ensure safe installation into a masonry,
UL127-listed manufactured fireplace or listed
vent-free firebox.
Minimum Clearances For Side
Combustible Material, Side Wall and
Ceiling
A. Clearances from the side of the fireplace
cabinet to any combustible material and
wall should follow diagram in Figure 4.
Example:
The face of a mantel, bookshelf,
etc. is made of combustible material and
protrudes 3
1
/
2
" from the wall. This com-
bustible material must be 4" from the side
of the fireplace cabinet (see Figure 4).
Note: When installing your gas logs into
a manufactured firebox, follow firebox
manufacturer’s instructions for minimum
clearances to combustible materials.
B. Clearances from top of fireplace opening
to ceiling should not be less than 42".
Figure 4 - Minimum Clearance for
Combustible to Wall
*Minimum 16" from Side Wall
*
Example
MINIMUM FIREPLACE CLEARANCE TO
COMBUSTIBLE MATERIALS
Side Wall 16", Ceiling 42", Floor 5",
Front 36"