VENTING INSTALLATION
Continued
Figure 14 - Typical Horizontal
Termination Cap Mounting with
Additional Siding Standoff Installed
Siding
Standoff
Screws
High Wind
Termination
Apply
Mastic to
Outside
Edge of
Standoff
Exterior Wall with Vinyl Siding
11
1
/
2
" x 11
1
/
2
"
Framed Opening
Maintain 1"
Minimum Air
Space Around
Outer Pipe When
Penetrating a Wall
Minimum
Pipe
Overlap
1
1
/
4
Wall
Firestop
Direct
Vent
Pipe
Horizontal Termination Configurations
Figures 15 and 16 show a configuration for
venting with horizontal termination with a chart
of critical minimum and maximum dimensions
which MUST be met.
If using a venting configuration of only hori
-
zontal venting with no vertical run, a ¼'' rise
for every 12'' of run toward the termination
is required.
NOTICE: Do not seal termination
cap to vent pipe. Cap must be
removable for vent inspection
and maintenance.
WARNING: Never run vent
downward as this may cause
excessive temperatures which
could cause a fire. Operation of
improperly installed and main
-
tained venting system could
result in serious injury, property
damage or loss of life.