TROUBLESHOOTING
Troubleshooting
Window 00 shows F1-F5, LU or OU
Fault handling according to
PROTECTION AND ALARM
(page 19).
Impossible to do Auto-set
Auto-set is disconnected during the Start-up delay period or if an alarm indication is
present.
The pump starts and stops too often or seldom, or the level in the pit is too low or too high
Change the settings in window 21 and window 22 according to
Start conditions and pause
time adjustment
(page 14).
The pump stops although it is not snoring
Check the stop level value in window 11. This value is probably too high in relation to
measured power in window 04. The pump operating power may have decreased due to
worn out hydraulic parts. Perform a new AUTOSET according to
DETAILED SETTINGS
(page 11) or change hydraulic parts if necessary. If hydraulic parts are changed, a new
AUTOSET has to be performed.
The pump doesn’t stop when snoring
Check the stop level value in window 11. This value is probably too low in relation to
measured power in window 04. Perform a new AUTOSET according to
DETAILED
SETTINGS
(page 11).
The value in window 04 increases when the pump starts to snore
Check that the current transformer(s) is linked to the phase connected to terminal 9 (L1).
“oor” (out of range) is shown on the display
This means that the value is too big to be shown on the display. The values in windows 06,
07 and 08 can be set to 0 by pressing – and + simultaneously for three seconds.
FPC100 unit is damaged or “dead“
• Component failure in FPC100. FPC100 has to be changed.
• Power supply to FPC100 (L2 or/and L3) is interrupted. Check wiring.
TROUBLESHOOTING
Single pump controller Installation and user manual for FPC100
21
Summary of Contents for FPC100
Page 1: ...Single pump controller Installation and user manual for FPC100...
Page 2: ......
Page 27: ......