FLYGT FPC100 Installation And User Manual Download Page 1

Single pump controller

Installation and user

manual for FPC100

Summary of Contents for FPC100

Page 1: ...Single pump controller Installation and user manual for FPC100...

Page 2: ......

Page 3: ...NT PANEL LAYOUT AND FUNCTION KEYS 9 Front panel layout and function keys 9 DISPLAY SYMBOLS AND UNITS 10 Display symbols and units 10 DETAILED SETTINGS 11 General 11 Lock and unlock menu settings 11 Re...

Page 4: ...y voltage to FPC100 and set the Hand 0 Auto switch in the Auto position The pump shall now be pumping water without drawing air If the pump doesn t start press START RESET 3 When the pump is working s...

Page 5: ...lsiasi lavoro controllare che la centralina degli automatismi sia staccata dalla rete di alimentazione elettrica e che non sia sotto tensione Controleer voordat u begint te werken of de schakelkast ge...

Page 6: ...l Xylem sales office Keep the packing It can be needed for return of the delivery or in case of inspection at damage The housing of the FPC100 is made of recyclable plastic type PC ABS The circuit boa...

Page 7: ...be found in TECHNICAL SPECIFICATIONS page 22 PE L1 L2 L3 N M 3 Max 240VAC Hand I Dig in Temp Alarm Pump 1 3 4 5 7 8 6 9 L1 11 L2 L3 13 2 Supply Auto 0 Alarm Auto set Reset High level Thermistor PTC o...

Page 8: ...gh the current transformer core an additional number of turns to put the available transformer capacity to full use The formula below can be used to determine how many turns the phase conductor of the...

Page 9: ...oice and adaptation of current transformer page 6 Connect the CT secondary winding to terminals 1 and 2 Note The CT must be linked to the phase connected to terminal 9 L1 Supply voltage connection Con...

Page 10: ...enable immediate start of the pump 2 External Reset 3 External Auto set Terminal 5 connection e g temperature supervision Terminals 4 and 5 can be used for temperature supervision a thermal contact o...

Page 11: ...10 Key Function RESET START Resets a latched alarm Starts pump motor AUTO SET Sets the stop level when pressed for 3 s NEXT Proceeds to the next window Decreases the displayed value For fast decrement...

Page 12: ...07 is 13467 hours Window number 07 is displayed for 2 sec and then 13467 is displayed for 2 sec Symbol Meaning Alarm Time value Parameter lock Unit Meaning V Volt mA Milli ampere m Minutes S Seconds P...

Page 13: ...9 to 369 and confirm with ENTER A padlock is shown indicating access only to windows 00 09 Re entering value 369 and confirming with ENTER gives access to all windows Returning to default settings If...

Page 14: ...dlock and get access to parameter settings windows 11 99 4 Clear the present stop level by pressing AUTOSET until SEt is shown on the display The stop level is hence set to 0 since the pump is off 5 S...

Page 15: ...noring 6 Set the Hand 0 Auto switch in the Auto position to start the pump If necessary press START RESET 7 Run the pump until it starts to snore 8 Press AUTOSET until SEt is shown on the display The...

Page 16: ...use Calculation of pause time is based on previous pumping and pause times and is controlled by the two parameters level setting window 21 and maximum pause time window 22 The parameters can be adjust...

Page 17: ...ump start Standard window during pause Symbol is flashing together with m or S 720 15 min 900 0 s 02 Pumping time since the latest pump start Standard window when pumping Symbol is flashing together w...

Page 18: ...999 0 11 Stop level power in 0 125 0 12 Snore margin in 0 125 10 13 Type of Auto Set AUTOSET is pressed at normal pumping when pump doesn t snore AUTOSET is pressed at snoring or dry running _ or _ 21...

Page 19: ...nore detection until the pump is stopped 1 90 s 2 s 25 Pump starts when pause time is finished OFF means start only on high level set window 53 to 1 on OFF on 31 Terminal 5 supervision e g temperature...

Page 20: ...normally open nc no nc 53 Digital input for closing contact 1 High level switch gives immediate start of the pump 2 External Reset 3 External Auto set 1 2 3 1 61 Measured current on terminals 1 and 2...

Page 21: ...the FPC100 Action Switch off the main supply Disconnected and swap positions of phases L2 and L3 Phase asymmetry F2 An F2 alarm is generated when the phase asymmetry on the supply voltage exceeds the...

Page 22: ...sed with any device using a voltage free opening contact such as a motor protection unit Terminal 5 supervision is activated when window 31 is set to on and the alarm is latched if window 32 is set to...

Page 23: ...ED SETTINGS page 11 or change hydraulic parts if necessary If hydraulic parts are changed a new AUTOSET has to be performed The pump doesn t stop when snoring Check the stop level value in window 11 T...

Page 24: ...AC Pilot duty AC12 Fuse Max 10 A Terminal wire size Use 75 C copper Cu wire only 0 2 4 mm2 single core 0 2 2 5 mm2 flexible core stripped length 8 mm Terminal tightening torque 5 7 lbs in 0 56 0 79 Nm...

Page 25: ...s A limits for radio noise emissions from digital apparatus as set out in the Canadian interference Causing Equipment Regulations Part numbers FPC100 including current transformer CT Pump main voltage...

Page 26: ...Contains Dimension Parts Screws 4 pcs TECHNICAL SPECIFICATIONS 24 Single pump controller Installation and user manual for FPC100...

Page 27: ......