Window
Function
Value/Range
Default setting
Own settings and
comments
07
Total pumping time
in hours. Symbol
is displayed.
Press + and –
simultaneously for 3
sec to set the value to
0.
0–99999
0
08
Total number of
pump starts. Press +
and – simultaneously
for 3 sec to set the
value to 0.
0–99999
0
09
Parameter lock.
Symbol
is displayed when
parameters are
locked. Enter 369 to
lock/unlock window
11-99.
0–999
0
11
Stop level (power) in
%
0–125 %
0 %
12
Snore margin in %
0–125 %
10 %
13
Type of Auto Set.
AUTOSET is pressed at
normal pumping
when pump doesn’t
snore ( ¯ ).
AUTOSET is pressed at
snoring or dry
running ( _ )
¯ or _
( ¯ )
21
Level setting (used
for pause time
calculation).
Higher value
increases the
calculated pause
time. Example: the
value 3.2 gives 3.2
times longer pause
time than 1.0.
The level setting can
preferable be
adjusted after some
pump cycles in order
to adjust the pause
times, and hence the
level in the pit.
1.0–10.0
1.0
DETAILED SETTINGS
16
Single pump controller Installation and user manual for FPC100