Action:
• See
Choice and adaptation of current transformer
(page 6) for correct choice and
adaptation of current transformer(s).
Operation fault (F4)
If snoring is detected at the same time as the high level switch is activated, an-F4 alarm is
generated. The alarm relay is activated but the pump doesn’t stop. The fault can be
generated in two situations:
1. Correct snoring but faulty high level switch indication
Action:
• The high level switch can be stuck in the “high level” position. It can also be a short
circuit in the high level switch or in the cables between FPC100 and the high level
switch. The fault has to be corrected.
2. Correct high level switch indication but faulty snoring
Action:
• The stop level is above the normal pumping power. This can be the result if
hydraulic parts (e.g. the impeller) are worn out, resulting in lower power
consumption than normal. Perform a new AUTOSET or check the hydraulic part of
the pump. In either case a new AUTOSET has to be performed.
Fault terminal 5 (F5) e.g. high motortemperature
In case the pump motor is overheated, an F5-alarm is generated and the pump is stopped.
As an alternative the TEMP-input can be used with any device using a voltage-free opening
contact such as a motor protection unit.
Terminal 5 supervision is activated when window 31 is set to “on”, and the alarm is latched
if window 32 is set to “on”.
Action:
• If the alarm is not latched, the pump will start again if the fault disappears, e.g. when
the pump motor has cooled down.
• If the alarm is latched, RESET when the fault has disappeared or correct the fault in
case the fault remains.
Under/Overvoltage (LU/OU)
When FPC 100 is switched on, the voltages on phases L1, L2 and L3 are checked. If a
wrong phase voltage is detected, LU (undervoltage) or OU (overvoltage) alarm is
generated. The pump will not start.
Under/overvoltage is detected if the phase voltage is outside the voltage range including
tolerance (e.g. 3×380-/–10%).
Note: Under/overvoltage supervision is only activated at start up when FPC100 is switched
on. The purpose with the supervision is to ensure that correct FPC100 (correct voltage
range) is used.
If L1 is interrupted when FPC100 is switched on, LU (undervoltage) alarm is generated.
Action:
Check that the rated voltage of FPC100 corresponds with the supplying line voltage. The
rated voltage can be found on the rating plate on the side of the control unit.
Check that L1 is not interrupted.
PROTECTION AND ALARM
20
Single pump controller Installation and user manual for FPC100