![FLYGT 3126.290 Installation, Operation And Maintenance Manual Download Page 29](http://html1.mh-extra.com/html/flygt/3126-290/3126-290_installation-operation-and-maintenance-manual_2311487029.webp)
Sensors
Value (mA)
Definition
FLS and thermal contact
0
Overtemperature
7.8
OK
36
Leakage
The values have a 10% tolerance.
T-installation: Bleed air before starting pump
1. Open valve D and bleed out the air. See the following figure.
WS008391B
A
C
B
1
2
3
D
4
1.
Outlet line
2.
Inlet line
3.
Line to drain
4.
Air vent
Figure 9: T-installation, valves A—D
2. Close valve D before the pump is started.
Check the impeller rotation
CAUTION: Crush Hazard
The starting jerk can be powerful. Make sure nobody is close to the unit when it is started.
1. Start the motor.
2. Stop the motor after a few seconds.
3. Check that the impeller rotates according to this illustration.
Installation
Flygt 3126.290 Installation, Operation, and Maintenance Manual
27
Summary of Contents for 3126.290
Page 1: ...Installation Operation and Maintenance Manual Flygt 3126 290 ...
Page 2: ......
Page 47: ......