RS485
Wiring
61
7
Figure 7-4: Wiring the Sensor’s RS485 Interface with USB/RS485 Converter in 2-Wire Mode
7.3.4 Multiple Sensors
For an installation of two or more sensors in a RS485 network (2-wire, half duplex), each sensor needs its specific
RS485 network address (1 - 32). Once all the units are addressed, wire up the units in the 2-wire multidrop manner,
whereas all A and B signals must be connected to common lines. The common A signals must be routed to the
TX+ and the common B signals to TX- terminal at the USB/RS485 converter given below.
Addressing
If you are installing two or more sensors in a multi-drop configuration, please be aware of the following:
•
Each sensor must have a unique address greater zero (1 - 32).
•
Each sensor must be set to the same baud rate (default is 9.6 kBaud).
•
Once all the units are addressed, wire up the units in the 2-wire multidrop manner, keeping all A & B to
be common.
•
Now you can run the supplied software, as well as written communication software or an individual
terminal program to access the sensor for issuing commands and receive the responses.
Figure 7-5: Wiring the Multiple Sensors via RS485 Interface with USB/RS485 Converter in 2-Wire Mode
USB/RS485 Converter
Sensor
A of 3
rd
sensor
B of 3
rd
sensor
A of 2
nd
sensor
B of 2
nd
sensor
To the 1
st
sensor
www.
.com
1.800.561.8187