DSX-602 CableAnalyzer
Users Manual
32
Table 2. Settings for Twisted Pair Tests
Setting
Description
Cable Type
Select a cable type that is correct for the type you will
test. To see a different group of cable types, tap
MORE
,
then tap a group. To make a custom cable type, tap
Custom
in the
Cable Groups
list.
NVP
Nominal velocity of propagation. The tester uses the NVP
and the propagation delay to calculate the length of the
cable.
The default value is defined by the selected cable type
and is the typical NVP for that cable type. To enter a
different value, tap the
NVP
panel, then tap
or
on the
NVP
screen to increase or decrease the value.
To find the actual value for a cable, connect a known
length of the cable to the tester, tap
MEASURE
on the
NVP
screen, then change the NVP until the measured
length matches the known length. Use a cable at least
30 m (100 ft) long.
When you increase the NVP value, the calculated length
increases.
Shield Test
This setting shows only when you select a shielded cable
type.
On
: The wire map test includes a DC test for shield
continuity and AC tests for shield quality. The wire map
test fails if the shield is open or the AC test results are
unsatisfactory.
Off
: The wire map shows the shield if the shield has
continuity. The tester does not do AC tests for shield
quality. The wire map test does not fail or show the
shield if the shield is open.
Test Limit
Select the correct test limit for the job. To see a different
group of limits, tap
MORE
, then tap the name of a
group.