Page 34
FW-F093-P-M_v0404_01_EN.docx
Type OA
An active 24V DC transistor output is available with this option.
Max. driving capacity 400mA@24V DC. (Requires power supply type PF / PM)
Fig. 25: Terminal connections - Active transistor output (OA).
Type OR
An isolated mechanical relay output is available with this option.
Max. switch power 240V 0,5A. (Requires power supply type PF / PM).
Fig. 26: Terminal connections - Mechanic relay output (OR).
4.7.3
TERMINALS 5-7: TACHOMETER INPUT
Three basic types of tachometer signals can be connected to the F093-P: pulse, active pulse or coil.
The screen of the signal wire can be connected to the common ground terminal. See paragraph 4.5.
The input signal type has to be selected with the correct SETUP-function (read chapter 3.3.2).
On terminal 7, the internal or external tachometer supply is available. To configure the supply, see
paragraph 4.5.5: Tachometer supply for details.
Coil-signal
The F093-P is suitable for use with tachometers which have a coil output signal.
Two sensitivity levels can be selected with the SETUP-function:
•
COIL LO: sensitivity from about 90mVp-p.
•
COIL HI: sensitivity from about 20mVp-p.
•
Type ZF (option): offers for setting COIL HI : sensitivity from about 10mVp-p.
•
Type ZG (option): offers for setting COIL HI : sensitivity from about 5mVp-p.
Fig. 27: Terminal connections - Coil signal input.