background image

Page 23 

FW-F014-P-M_v0402_05_EN.docx 

Terminal 4-5: POWER SUPPLY UNIT - TYPE PD / PX: 

To power the F014-P an internal battery can be used (type PB) and / or an external DC power 
supply of  8-30V DC (type PX) or 16-30V DC (type PD).  

Connect the "

-

" to terminal 4 and the "

+

" to terminal 5.  

When power is applied to these terminals, the optional internal battery will be disabled / enabled 
automatically to extend the battery life time. 

Terminal 6: Power supply type PD: 8.2V sensor supply. 

With this option, a limited power supply for the sensor is available, for example to power a Namur 
sensor. It offers 8.2V DC (max. 5mA).  

 

 

This terminal is only available if option PD has been ordered 

 

Terminal 7-8; Pulse output 

– type OT: 

With SETUP 6, the function of this output is set to a scaled pulse output. 

A passive transitor output is available with this option. 

Max. driving capacity 300mA@50V DC. 

 

Fig. 15: Terminal connections - Passive transistor output. 

 

Terminal 9-10: Power supply backlight - type ZB (option): 

To power the backlight, a voltage in the range 20-30V DC has to be connected.  

Maximum current 30mA. Connect the "

-

" to terminal 9 and the "

+

" to terminal 10.  

Summary of Contents for F014-P

Page 1: ...ITH SCALED PULSE OUTPUT Signal input flowmeter pulse Namur and coil Output one scaled pulse ref accumulated total Options Intrinsically Safe F Series Field mounted indicators for safe and hazardous areas More info www fluidwell com fseries ...

Page 2: ...ould be disposed of according to local regulations regarding waste electronic equipment If a battery is present in this product it should be disposed of separately The separate collection and recycling of your waste equipment will help to conserve natural resources and ensure that it is recycled in a manner that protects the environment SAFETY RULES AND PRECAUTIONARY MEASURES The manufacturer acce...

Page 3: ...ns or procedures which if not performed correctly may lead to personal injury a safety hazard or damage of the F014 P or connected instruments A caution indicates actions or procedures which if not performed correctly may lead to personal injury or incorrect functioning of the F014 P or connected instruments A note indicates actions or procedures which if not performed correctly may indirectly aff...

Page 4: ...enu 7 Others 15 4 INSTALLATION 16 4 1 General directions 16 4 2 Installation surrounding conditions 16 4 3 Dimensions Enclosure 17 4 4 Installing the hardware 19 4 4 1 Introduction 19 4 4 2 Terminal connectors with power supply type PB PD PX 20 4 4 3 Terminal connectors with power supply type PF PM 24 5 INTRINSICALLY SAFE APPLICATIONS 29 5 1 General information and instructions 29 5 2 Terminal con...

Page 5: ...14 P To power the sensor several options are available Fig 1 Typical application for the F014 P Configuration of the F014 P The F014 P has been designed to be implemented in many types of applications For that reason a SETUP level is available to configure your F014 P according to your specific requirements It includes several important features such as K Factor measurement units signal selection ...

Page 6: ...his instruction is meant for users operators 2 2 CONTROL PANEL The following keys are available Fig 2 Control panel Functions of the keys This key is used to program and save new values or settings It is also used to gain access to SETUP level please read chapter 3 This key is used to SELECT accumulated total The arrow key is used to increase a value after PROG has been pressed or to configure the...

Page 7: ...nd flowrate on the bottom line It is possible to display flowrate only with the large 17mm digits in this instance press the SELECT key to read the total When is shown then the flowrate value is too high to be displayed The arrows indicate the increase decrease of the flowrate trend Clear total The value for total can be re initialized To do so press CLEAR twice After pressing CLEAR once the flash...

Page 8: ...ty All instructions in this manual are to be observed Ensure that the measuring system is correctly wired up according to the wiring diagrams The housing may only be opened by trained personnel Take careful notice of the Safety rules instructions and precautionary measures in the front of this manual 3 2 PROGRAMMING SETUP LEVEL 3 2 1 GENERAL INFORMATION Configuration of the F014 P is done at SETUP...

Page 9: ...as a unique number which is displayed below the word SETUP at the bottom of the display The number is a combination of two figures The first figure indicates the function group and the second figure the sub function Additionally each function is expressed with a keyword After selecting a sub function the next main function is selected by scrolling through all active sub functions e g 1 11 12 13 14...

Page 10: ...mming To select a setting is used to select in one direction and can be used to select in the other direction When data is altered but ENTER is not pressed then the alteration can still be cancelled by waiting for 20 seconds or by pressing ENTER for three seconds the PROG procedure will be left automatically and the former value reinstated Alterations will only be set after ENTER has been pressed ...

Page 11: ... 0 000010 9 999 999 25 DECIMALS K FACTOR 0 6 26 CALCULATION per 1 255 pulses 27 CUT OFF 0 1 999 9 seconds 3 DISPLAY 31 FUNCTION total flowrate 32 BACKLIGHT optional off green amber 33 BL BRIGHTNESS 1 5 4 POWER MANAGEMENT 41 LCD NEW fast 1 sec 3 sec 15 sec 30 sec off 42 BATTERY MODE operational shelf 5 FLOWMETER 51 SIGNAL npn npn_lp reed reed_lp pnp pnp_lp namur coil_hi coil_lo active 6 PULSE outpu...

Page 12: ...or example per cubic meter The more accurate the K factor the more accurate the functioning of the system will be Example 1 Calculating the K factor Let us assume that the flowmeter generates 2 4813 pulses per liter and the selected unit is cubic meters m3 A cubic meter consists of 1000 parts of one liter which implies 2 481 3 pulses per m3 So the K factor is 2 481 3 Enter for SETUP 13 2481300 and...

Page 13: ...the flowmeter per selected measurement unit SETUP 21 for example per liter The more accurate the K factor the more accurate the functioning of the system will be For examples read SETUP 13 25 DECIMALS K FACTOR This setting determines the number of decimals for the K factor SETUP 24 The following can be selected 0 1 2 3 4 5 6 Please note that this SETUP influences the accuracy of the K factor indir...

Page 14: ...hese functions are available SETUP FUNCTIONS AND VARIABLES 4 POWER MANAGEMENT 41 LCD NEW The calculation of the display information influences the power consumption significantly When the application does not require a fast display update it is strongly advised to select a slow refresh rate Please understand that NO information will be lost every pulse will be counted and the output signal will be...

Page 15: ... p t p Normal sensitivity ACTIVE Active pulse input detection level 1 2V DC 47 kΩ 10 kHz External power required 3 2 8 EXPLANATION OF SETUP MENU 6 PULSE OUTPUT SETUP FUNCTIONS AND VARIABLES 6 PULSE OUTPUT 61 PULSE WIDTH The pulse width determines the time that the output will be switched in other words the pulse length The minimum time between the pulses is as long as the period time 50 50 duty cy...

Page 16: ...our supplier will ask for this information in the case of a serious breakdown or to assess the suitability of your model for upgrade considerations 73 SERIAL NO For support and maintenance it is important to have information about the characteristics of the F014 P Your supplier will ask for this information in the case of a serious breakdown or to assess the suitability of your model for upgrade c...

Page 17: ...e the relevant IP classification of the enclosure into account see identification plate Even an enclosure rated for IP67 TYPE 4 X should NEVER be exposed to strongly varying weather conditions When panel mounted the front panel of the F Series is rated for IP65 TYPE 4 X When used in very cold surroundings or varying climatic conditions inside the instrument case take the necessary precautions agai...

Page 18: ...60 mm 2 36 120 mm 4 72 M20 x 1 5 PG9 PG9 30mm 30mm 22 5mm M20 x 1 5 M16 x 1 5 M16 x 1 5 30mm 30mm 22 50mm M20 x 1 5 22 5mm M20 x 1 5 M20 x 1 5 25mm 25mm 22 5mm 1 2 NPT 0 9 3x 1 2 NPT 0 12 0 12 0 9 HA HM HN HO HP HT HU 6 x M12 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 115 mm 4 53 98 mm 3 86 HB 29 1 mm 1 15 31 mm 1 22 HZ 4x M20 x 1 5 15 15 15 HV 23 23 16 mm ...

Page 19: ...40 60 mm 2 36 120 mm 4 72 HD HK HK back box flat bottom HE HF HG HH D 12mm 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 22 5mm 30mm 30mm D 16mm D 20mm 0 9 D 22mm 0 866 22 5mm 25mm 25mm D 20mm D 20mm D 16mm HC 75 mm 2 95 118 mm 4 65 104 mm 4 09 HJ 0 9 0 12 0 12 3x D 22mm 0 866 115 mm 4 53 98 mm 3 86 29 1 mm 1 15 31 mm 1 22 ...

Page 20: ...lied with the 115 230V AC power supply type PM The green yellow wire between the back casing and removable terminal block may never be removed Fig 7 Grounding aluminum enclosure with option PM 115 230 V AC FOR INSTALLATION PAY EMPHATIC ATTENTION TO Separate cable glands with effective IP67 NEMA4X seals for all wires Unused cable entries ensure that you fit IP67 NEMA4X plugs to maintain rating A re...

Page 21: ...ible to use some low power NPN or PNP output signals but the battery life time will be significantly reduced consult your distributor Type PD terminal 6 sensor supply 8 2V This option offers a basic sensor supply of max 5mA 8 2V to power e g a Namur sensor REMARKS TERMINAL CONNECTORS Terminals 1 3 Flowmeter input Three basic types of flowmeter signals can be connected to the F014 P pulse active pu...

Page 22: ...erminal connections NPN signal input Pulse signal PNP PNP LP The F014 P is suitable for use with flowmeters which have a PNP output signal Terminal 3 offers 3 2V which has to be switched by the sensor to terminal 2 SIGNAL For a reliable pulse detection the pulse amplitude has to go above 1 2V Signal setting PNP LP employs a low pass signal noise filter which limits the maximum input frequency read...

Page 23: ... switch To avoid pulse bounce from the reed switch it is advised to select REED LP low pass filter read chapter 3 2 3 Fig 13 Terminal connections Reed switch signal input NAMUR signal The F014 P is suitable for flowmeters with an NAMUR signal The standard F014 P is not able to power the NAMUR sensor as an external power supply for the sensor is required However a 8 2V sensor supply voltage termina...

Page 24: ... supply With this option a limited power supply for the sensor is available for example to power a Namur sensor It offers 8 2V DC max 5mA This terminal is only available if option PD has been ordered Terminal 7 8 Pulse output type OT With SETUP 6 the function of this output is set to a scaled pulse output A passive transitor output is available with this option Max driving capacity 300mA 50V DC Fi...

Page 25: ...th the three switches inside the F014 P Be sure that all the leads to the terminals are disconnected from the F014 P when the internal plastic protection cover has been removed HIGH VOLTAGE 400V NEVER connect the mains power supply to the F014 P when the plastic protection cover has been removed First remove the terminal strip s after which the internal plastic cover can be removed The switches ar...

Page 26: ... Terminal 3 4 Pulse output With SETUP 6 the function of this pulse output is determined with a maximum frequency of 500Hz Type OT A passive transistor output is available with this option Max driving capacity 300mA 50V DC Fig 18 Terminal connections Passive transistor output OT Type OA An active 24V DC transistor output is available with this option Max driving capacity 400mA 24V DC Requires power...

Page 27: ...s can be selected with the SETUP function COIL LO sensitivity from about 90mVp p COIL HI sensitivity from about 20mVp p Type ZF option offers for setting COIL HI sensitivity from about 10mVp p Type ZG option offers for setting COIL HI sensitivity from about 5mVp p Fig 21 Terminal connections Coil signal input Pulse signal NPN NPN LP The F014 P is suitable for use with flowmeters which have a NPN o...

Page 28: ...read chapter 3 2 3 A sensor supply voltage is offered with terminal 7 Fig 23 Terminal connections PNP signal input Active signals Active signal selection may well be desired if an active signal is offered from the sensor Fig 24 Terminal connections Active signal input Reed switch The F014 P is suitable for use with flowmeters which have a reed switch To avoid pulse bounce from the reed switch it i...

Page 29: ...v0402_05_EN docx NAMUR signal The F014 P is suitable for flowmeters with an NAMUR signal Terminal 7 can provide a 8 2V sensor supply voltage please read section sensor supply Fig 26 Terminal connections NAMUR signal input ...

Page 30: ...ement instructions Mounting electrical installation start up and maintenance of this device may only be carried out by trained personnel authorized by the operator of the facility Personnel must read and understand this Operating Manual before carrying out its instructions This device may only be operated by personnel who are authorized and trained by the operator of the facility All instructions ...

Page 31: ...y Safe Possible static hazard Do not rub KEMA 05ATEX1168 X IECEx KEM 08 0006X II 1 G Ex ia IIC T4 II 1 D Ex iaD 20 IP 65 67 T 100 C Ga Ex ia IIC T4 Ex iaD 20 IP 65 67 T 100 C Intrinsically Safe for Class I II III Div 1 Grps A B C D E F G Temp class T4 Class I Zone 0 AEx ia IIC T4 For installation and entity evaluation refer to control drawing no FWCD 0003 CSA Certificate nr CSA 08 2059461 FM Proje...

Page 32: ...Y POWERED IIA IIB IIC Fig 30 F014 P OT PC PX XI ZB Battery powered Intrinsically Safe application Sensor supply voltage for pulse type P Terminal 3 1 2 3 2V DC Please note Type PX may be used in combination with the battery Type PC PX will power the F014 P the battery will be disabled automatically until the power is disconnected ...

Page 33: ...the battery Type PC PX will power the F014 P the battery will be disabled automatically until the power is disconnected 5 3 3 F014 P OT PX XI ZB IIA IIB IIC Fig 32 F014 P OT PX XI ZB Intrinsically Safe application Sensor supply voltage for pulse type P Terminal 3 1 2 3 2V DC Please note Type PX may be used in combination with the battery Type PC PX will power the F014 P the battery will be disable...

Page 34: ...PD XI ZB Intrinsically Safe application Sensor supply voltage for pulse type P Terminal 3 1 2 3 2V DC Terminal 6 8 2V DC Please note Type PD may be used in combination with the battery Type PC PD will power the F014 P the battery will be disabled automatically until the power is disconnected ...

Page 35: ...with the utmost care to prevent a short circuit and damage 4 Do not recharge crush disassemble incinerate heat above its rated temperature or expose the contents to water 5 Dispose of the battery in accordance with the inter national the manufacturer s and the plant owner s standards and regulations 6 Read and understand the instructions 7 Get approval from the safety officer to do the work 8 Lock...

Page 36: ...lity to take all precautions to dehumidify the internal atmosphere of the F014 P in such a way that no condensation will occur for example by placing dry silica gel sachet in the casing just before closing it Furthermore it is required to replace or dry the silica gel periodically as advised by the silica gel supplier Battery life time It is strongly advised to use only necessary functions It is i...

Page 37: ... HC Type HB Dimensions 130 x 120 x 60mm 5 10 x 4 72 x 2 38 LxHxD IP65 NEMA4 115 x 98mm 4 53 x 3 86 LxH GRP panel mount enclosure Aluminum panel mount enclosure Field wall mount enclosures Classification Aluminum enclosures Type HA Type HM Type HN Type HO Type HP Type HT Type HU Type HV Type HZ GRP enclosures Type HD Type HE Type HF Type HG Type HJ Type HH Type HK ABS enclosure Type HS Dimensions 1...

Page 38: ...s is not a real sensor supply Only suitable for sensors with a very low power consumption like coils sine wave and reed switches Analog sensors type A U sensor supply not available Type PD With pulse input type P sensor supply 1 2 3 2 8 2V DC max 5mA 8 2V DC With analog input type A U as connected power supply voltage internally linked Type PF PM Analog sensors type A U sensor supply 8 2 12 and 24...

Page 39: ...times a second Voltage drop 2 6 Volt Load impedance 3kOhm Relationship Linear and square root calculation For signal type A and U external power to sensor is required e g type PD PF PM Output Pulse output Function Scaled pulse output max frequency 500Hz Type OT One passive transistor output not isolated Load max 50V DC 300mA Type OA One active 24V DC transistor output max 400mA per output requires...

Page 40: ... flag starts to blink an internal alarm condition has occurred Press the select button several times to display the 4 digit error code The codes are 0001 irrecoverable display data error data on the display might be corrupted 0002 irrecoverable data storage error the programming cycle might have gone wrong check programmed values 0003 error 1 and error 2 occurred simultaneously The alarm condition...

Page 41: ...DECLARATION OF CONFORMITY ...

Page 42: ...Page 41 FW F014 P M_v0402_05_EN docx CONTROL DRAWING ...

Page 43: ... unit 12 time unit 12 functional description 4 hardware version 2 high alarm output 23 intrinsic safety 29 Intrinsic safety 29 30 35 keys 5 main function 8 maintenance 35 manual version 2 namur signal 22 28 operational 5 7 16 35 operator level 6 pass code 39 power supply 23 25 pulse output 14 25 pulse length period time 14 pulse signal NPN 21 26 pulse signal PNP 21 27 rate total 6 reed switch 22 s...

Page 44: ...mals K factor 0 2 FLOWRATE 21 unit L 22 time unit min 23 decimals 0000000 24 K factor 0000001 25 decimals K factor 0 26 calculation pulses 010 27 cut off time 30 0 sec 3 DISPLAY 31 function total 32 backlight off 33 brightness 5 4 POWER MANAGEMENT 41 LCD new 1 sec 42 mode operational 5 FLOWMETER 51 signal coil lo 6 PULSE OUTPUT 61 pulse width 0 000 sec 62 decimals 0000000 63 pulse per 1000 L 7 OTH...

Reviews: