Integer Scalers
Several scaled integer registers provide access to process information using integer registers for
those devices that do not support floating point registers. These registers are listed in Table II.
The scaling registers must be set for the variable scale registers before the scaled value can be
interpreted. The minimum scale register sets the engineering value that will equal a register value of 0
and the maximum scale register sets the engineering value that will equal a register value of 9999.
SP3 Modbus
Register
Type
Range
Minimum
Scale Register
Maximum
Scale Register
Description
30018
RO 0 to 9999
70625
70627
Variable scale
normalized
liquid flow in
currently selected
engineering units.
30019
RO 0 to 9999
70629
70631
Variable scale
normalized
gas flow in
currently selected
engineering units.
30020
RO 0 to 9999
70633
70635
Variable scale
normalized P1
isa in currently
selected
engineering units.
30021
RO 0 to 9999
70637
70639
Variable scale
normalized P2
isa in currently