EchoSwitch II
09 JUL 08
MN300650
Rev
A
Getting around:
EchoSwitch II is configured by the use of three push buttons (UP, DOWN and SELECT) and a
LCD display. As a lockout feature, the buttons are inactive until the SELECT button is held
down for 5 seconds, and then the display will begin to scroll through the top level of the
configuration menu.
Top Level
•
The Configuration menu will continue to scroll through the items below until the
SELECT
button is pressed.
•
UNITS
–
TANK
–
RELAY 1
–
RELAY 2
–
RELAY 3
–
SAFE
– (
MPLEX) -
HELP
-
RUN
•
To return to the Operational mode of EchoSwitch, press SELECT while RUN appears in the
display.
•
UNITS
– Allows end user to select the units for configuration and operation. Select between
Inches, Centimeters, Feet, Meters or Percent. Press EXIT to return to the Top Level menu.
•
TANK
– Allows the end user to configure the operational range for the switch.
o
HEIGHT
– Distance from the transducer face to the bottom of the tank.
o
FILL-H
– Maximum fill height of the liquid from the bottom of the tank.
o
Press Exit to return to the Top level Menu
o
Note: if UNITS is set to Percent, then TANK will not appear. To view TANK, set
UNITS to any of the following: Inches, Centimeters, Feet or Meters
•
RELAY 1, 2 or 3
– Allows end user to configure the function and operation of each relay.
Each relay has a small black circle that appears when the relay is energized. When the relay
is de-energized, the black circle disappears.
o
PUMP
– Pump operation allows for two separate level set points (Relay ON and
Relay OFF). Choose between the EMPTY or FILL operation. Both operations
require setting a level for ON and another level for OFF
EMPTY
– used to control a pump that empties a tank.
Typically, Relay ON is the HIGH set point and Relay OFF the LOW set point.
Relay will energize at the high set point (ON) and remain on until the level
reaches the low set point (OFF) and will remain off until the level returns to
the high set point (ON).