FlowLine EchoSafe XP88 Owner'S Manual Download Page 9

C. Factory RESET:

1.  Press the SELECT/FAST button and hold it for 5 seconds until 

MENU appears.

2.  When HELP appears, press the SELECT/FAST button. The dis-

play will rotate between SETUP, TEST P and R ALL.

3.  When R ALL appears, press the SELECT/FAST button.
4.  Unit will reset.

Note:

 FACTORY RESET resets the transmitter back to its origi-

nal factory default settings: (20 mA = Minimum Range, 4mA = 

Maximum Range and SAFE = 22mA). 

D. Testing the Transmitter

1.  Connect a multi-meter in series 

with the black wire to read the 

current output. 

2.  Verify that the current increas-

es  (tank  filling)  and  decreases 

(tank  emptying)  appropriately 

in the calibrated span.

3.   If  not,  carefully  observe  and 

attempt to correlate any instal-

lation, level or application event 

for more specific troubleshoot-

ing.

4.   Write down the information in 

TEST P (SEGMENT, RANGE, 

ECHO, POWER, VER) and have it ready when you contact your 

Flowline representative.

E. Additional Information:

 Go to www.flowline.com and click 

on the nav-bar “Application Info” button for FAQ’s, tech-tips, case 

studies, white papers, glossary and success stories.

Step Fifteen

Step Fourteen

SELECT

FAST

SELECT

FAST

SELECT

FAST

0(18

:$,7

(;,7

TROUBLESHOOTING

Transmitter

XP88-0
XP89-0

4 mA Setting

26.4  (7.5m)

32.8  (10m)

20 mA Setting

8  (20 cm)

12  (30 cm)

Factory Set Points

Power

Supply

Power

Supply

20 mA

4 mA

mA

4

5

6

mA

19

20

21

Black

Red

EchoSafe

EchoSafe

Black

Red

TROUBLESHOOTING

A. Viewing Programmed VALUES:

1.  Press the SELECT/FAST button and hold it for 5 seconds until 

MENU appears.

2.  When HELP appears, press the SELECT/FAST button. The dis-

play will rotate between SETUP, TEST P and R ALL.  

3.  When SETUP appears, press the SELECT/FAST button. You will 

now begin viewing calibration settings (UNITS, HEIGHT, FILL 
H, SAFE, REV mA) that are programmed in the transmitter. 

When complete the display will revert back to the HELP menu.

B. Viewing TEST P:

1.  Press the SELECT/FAST button and hold it for 5 seconds until 

PROG appears.

2.  When VALUES  appears,  press  the  SELECT/FAST  button. The 

display will rotate between SETUP, TEST P and RESET.  

3.  When DIAG appears, press the SELECT/FAST button. You will 

now  begin  viewing  diagnostic  values  (LEVEL,  TEMP  ECHO, 
POWER, MOUNT and VER) that may be relevant to the trans-
mitter and it’s performance in your application.

When complete the display will revert back to the VALUES menu.

SELECT

FAST

SELECT

FAST

SELECT

FAST

0HQX

81,76

+(,*+7

),//+

6$)(

5(90$

'21(

SELECT

FAST

SELECT

FAST

SELECT

FAST

0(18

:$,7

5$1*(

9(5

Summary of Contents for EchoSafe XP88

Page 1: ...duct returned to Flowline where a There is evidence of a potentially hazardous material present with product b The product has remained unclaimed at Flowline for longer than 30 days after dutifully requesting disposition of the product THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE OF THIS WARRANTY This warranty and the obligations and liabilities of Flowline under it are ...

Page 2: ...lay type Display units Memory Supply voltage Loop resistance Signal output Signal invert Calibration Fail safe Process Temp Temp comp Electronics temp Pressure Enclosure rating Enclosure mat Window mat Transducer mat Process mount Conduit entrance Compliance Classification Approvals XP88 8 to 24 6 20 cm to 7 5 m XP89 8 to 32 8 20 cm to 10 m 0 2 of max range 0 079 2 mm 3 7 6 cm dia XP88 8 20 cm XP9...

Page 3: ...hin the fitting Always check for leaks prior to system start up Opening The Enclosure EchoSafe is designed to be installed in a hazardous areas and when installed do not open the unit while power is applied Always disconnect the power source from EchoSafe prior to opening programming install ing or removing it Additionally ensure that electrical wiring fittings and mechanical connections conform t...

Page 4: ...ammed FULL set point C EMPTY Level has reached the programmed EMPTY set point D UNITS Selectable in inches centimeters feet meter or percent The factory default is Inches E INCHES Inch units of measurement F CM Centimeters units of measurement G FEET Feet units of measurement H METERS Meter units of measurement I PERCNT 0 100 units of measurement Percent is the calcu lated value based on the 4mA a...

Page 5: ...olding down the SELECT FAST button while pressing the UP or DOWN button will increase the speed of the display Step Seven PROGRAMMING A Introduction The transmitter has two modes RUN and MENU In the RUN mode the transmitter is operational and the dis play will indicate the liquid height in inches centimeters or percent In the MENU mode the display will indicate the selected mode of calibration The...

Page 6: ...g UNITS To change UNITS from INCHES to CM or PERCENT 1 Press the SELECT FAST button and hold it for 5 seconds until MENU appears 2 When UNITS appears press the SELECT FAST button The dis play will rotate between INCHES CM FT M PERCENT and DISPLAY 3 Press the SELECT FAST button when the UNITS you want INCHES CM FT M or PERCENT appear The display will then display SAVED You have successfully changed...

Page 7: ...e to the HEIGHT value will result in an equal increase to the FILL H value A decrease to the HEIGHT value will result in an equal decrease to the FILL H value Step Eleven PROGRAMMING EchoSafe EchoSafe 4 mA 20 mA 20 mA 4 mA SELECT FAST SELECT FAST SELECT FAST 0HQX 7 EchoSafe 20 mA 4 mA Normal mA Mode 4 mA set at empty tank and 20 mA set at full tank Reverse mA Mode 20 mA set at empty tank and 4 mA ...

Page 8: ...Do not install within 3 of tank side wall Do not install with objects in the beam Do not install in applications with vacuum EchoSafe Dead Band Ventilation Hole Operational Range Highest Liquid Level Lowest Liquid Level 3 Minimum Diameter EchoSafe Warning Flowline Ultrasonic transmitters have been optimized for use in non metallic fittings For best performance avoid the use of metal fittings Insta...

Page 9: ...T FAST SELECT FAST SELECT FAST 0 18 7 7 TROUBLESHOOTING Transmitter XP88 0 XP89 0 4 mA Setting 26 4 7 5m 32 8 10m 20 mA Setting 8 20 cm 12 30 cm Factory Set Points Power Supply Power Supply 20 mA 4 mA mA 4 5 6 mA 19 20 21 Black Red EchoSafe EchoSafe Black Red TROUBLESHOOTING A Viewing Programmed VALUES 1 Press the SELECT FAST button and hold it for 5 seconds until MENU appears 2 When HELP appears ...

Reviews: