FlowLine EchoSafe XP88 Owner'S Manual Download Page 4

Step Four

PREPARATION

A. Supply Voltage:

 The transmitter power supply voltage should 

never  exceed  a  maximum  of  28  VDC.    Flowline  controllers  and 
meters have built-in 24 VDC power supplies for use with the trans-
mitter.  Alternative controllers and/or power supplies with a minimum 
output of 18 VDC may also be used with the transmitter for calibra-
tion and/or operation. 

B. Factory Span:

  All transmit-

ter models are factory calibrated with 
4 mA at their maximum range (tank 
empty) and 20 mA at their minimum 
range (tank full).  The 4 and 20 mA 
span  set  points  can  be  reverse  cali-
brated on all models.

C. Maximum Applied Range: 

The Individual or cumulative 

effects of agitation or vapor can reduce the overall quality of signal 
return  and  shorten  the  maximum  applied  range  of  the  transmitter.  
To determine the maximum applied range of the transmitter in your 
application, refer to the below de-rating chart.

50Khz

0

1

2

3

4

5

6

7

8

9

10

0%

50%

100%

Ultrasonic  Derating Chart

LU12-5__1

LU13-5__1 & LU14-5__1

Agitation = 1 - 5 @100Khz

Agitation = 1 - 7 @50Khz

Temp

= 3 @100Khz

Temp

= 3 @50Khz

Foaming = 4 - 6 @100Khz

Foaming = 7 - 9 @50Khz

Solids

= 5 - 6 @100Khz

Solids

= 7.5 @50Khz

Maximum Applied Range De-rating Chart

XP88/89-0

 

Agitation  =  1-3 @ 50 kHz

 

Vapor 

=  3-5 @ 50 kHz

 

Step Five

MENU ITEMS

A. WARM UP:

 This is the initial power up mode. When this mes-

sage is displayed, the transmitter is going through its power up rou-

tine, and validating the target value. After a short period of time, this 

message will disappear and be replaced by a numeric value.

B. FULL:

 Level has reached the programmed FULL set point.

C. EMPTY:

 Level has reached the programmed EMPTY set point

D. UNITS:

 Selectable in inches centimeters, feet, meter or percent. 

The factory default is Inches.

E. INCHES:

 Inch units of measurement.

F. CM:

 Centimeters units of measurement.

G. FEET: 

Feet units of measurement.

 

H. METERS: 

Meter units of measurement.

I.  PERCNT:

 0-100% units of measurement. Percent is the calcu-

lated value based on the 4mA and 20mA set points.

J. TANK:

 Menu through which the 

4-20 mA span is adjusted.

K.  HEIGHT:

  The  point  in  inches, 

feet, meters, or centimeters from the 

transducer face where the output will 

be 4 mA (generally the bottom of the 

tank).  Factory default is the same as 

the unit’s maximum range. Example: 

XP88 = 295” maximum range which 

is also the same 4 mA set point under 

factory default.

L. Fill H (Fill Height):

 The point 

in inches, feet, meters or centimeters 

from  the  bottom  of  the  tank  to  the 

high  level  where  the  output  will  be 

20  mA  (generally  the  straight  wall 

distance from the bottom of the tank). 

NOTE:  The  transmitter  dead  band 

is  automatically  subtracted  from  the 

FILL  H.  Example:  XP88  =  8”  dead 

band. Therefore the maximum FILL 

H  is  295”  [maximum  range]  -  8” 

[dead band] = 287”.

M. REV mA (Reverse mA):

 Allows the user to select 20 mA at 

the bottom and 4 mA at the top of the tank (20-4 mA). Factory default 

is 4 mA (MaxR) at the bottom and 20 mA (MinR) at the top. 

N. NORM: 

Sets EchoSafe so 4 mA is at the bottom of the tank and 

20 mA at the top. This is the default settings. 

O. REV: 

Sets EchoSafe so 20 mA is at the bottom of the tank and 

4 mA at the top. 

EchoSafe

EchoSafe

HEIGHT

(MaxR)

EMPTY

FULL

FILL H

(MinR)

EchoSafe

EchoSafe

HEIGHT

(MaxR)

EMPTY

FULL

FILL H

(MinR)

EchoSafe

EchoSafe

4 mA

20 mA

20 mA

4 mA

XP89-0

Reverse Mode

Summary of Contents for EchoSafe XP88

Page 1: ...duct returned to Flowline where a There is evidence of a potentially hazardous material present with product b The product has remained unclaimed at Flowline for longer than 30 days after dutifully requesting disposition of the product THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE OF THIS WARRANTY This warranty and the obligations and liabilities of Flowline under it are ...

Page 2: ...lay type Display units Memory Supply voltage Loop resistance Signal output Signal invert Calibration Fail safe Process Temp Temp comp Electronics temp Pressure Enclosure rating Enclosure mat Window mat Transducer mat Process mount Conduit entrance Compliance Classification Approvals XP88 8 to 24 6 20 cm to 7 5 m XP89 8 to 32 8 20 cm to 10 m 0 2 of max range 0 079 2 mm 3 7 6 cm dia XP88 8 20 cm XP9...

Page 3: ...hin the fitting Always check for leaks prior to system start up Opening The Enclosure EchoSafe is designed to be installed in a hazardous areas and when installed do not open the unit while power is applied Always disconnect the power source from EchoSafe prior to opening programming install ing or removing it Additionally ensure that electrical wiring fittings and mechanical connections conform t...

Page 4: ...ammed FULL set point C EMPTY Level has reached the programmed EMPTY set point D UNITS Selectable in inches centimeters feet meter or percent The factory default is Inches E INCHES Inch units of measurement F CM Centimeters units of measurement G FEET Feet units of measurement H METERS Meter units of measurement I PERCNT 0 100 units of measurement Percent is the calcu lated value based on the 4mA a...

Page 5: ...olding down the SELECT FAST button while pressing the UP or DOWN button will increase the speed of the display Step Seven PROGRAMMING A Introduction The transmitter has two modes RUN and MENU In the RUN mode the transmitter is operational and the dis play will indicate the liquid height in inches centimeters or percent In the MENU mode the display will indicate the selected mode of calibration The...

Page 6: ...g UNITS To change UNITS from INCHES to CM or PERCENT 1 Press the SELECT FAST button and hold it for 5 seconds until MENU appears 2 When UNITS appears press the SELECT FAST button The dis play will rotate between INCHES CM FT M PERCENT and DISPLAY 3 Press the SELECT FAST button when the UNITS you want INCHES CM FT M or PERCENT appear The display will then display SAVED You have successfully changed...

Page 7: ...e to the HEIGHT value will result in an equal increase to the FILL H value A decrease to the HEIGHT value will result in an equal decrease to the FILL H value Step Eleven PROGRAMMING EchoSafe EchoSafe 4 mA 20 mA 20 mA 4 mA SELECT FAST SELECT FAST SELECT FAST 0HQX 7 EchoSafe 20 mA 4 mA Normal mA Mode 4 mA set at empty tank and 20 mA set at full tank Reverse mA Mode 20 mA set at empty tank and 4 mA ...

Page 8: ...Do not install within 3 of tank side wall Do not install with objects in the beam Do not install in applications with vacuum EchoSafe Dead Band Ventilation Hole Operational Range Highest Liquid Level Lowest Liquid Level 3 Minimum Diameter EchoSafe Warning Flowline Ultrasonic transmitters have been optimized for use in non metallic fittings For best performance avoid the use of metal fittings Insta...

Page 9: ...T FAST SELECT FAST SELECT FAST 0 18 7 7 TROUBLESHOOTING Transmitter XP88 0 XP89 0 4 mA Setting 26 4 7 5m 32 8 10m 20 mA Setting 8 20 cm 12 30 cm Factory Set Points Power Supply Power Supply 20 mA 4 mA mA 4 5 6 mA 19 20 21 Black Red EchoSafe EchoSafe Black Red TROUBLESHOOTING A Viewing Programmed VALUES 1 Press the SELECT FAST button and hold it for 5 seconds until MENU appears 2 When HELP appears ...