FlowLine EchoSafe XP88 Owner'S Manual Download Page 3

Step Two

SAFETY

Step Three

OVERVIEW

A. Application:

  The explosion proof ultrasonic transmitter pro-

vides non-contact level detection up to 32.8’ or 10m. The transmitter 
is well suited for a wide range of corrosive, waste and slurry type 
media, and is broadly selected for atmospheric bulk storage, day tank 
and waste sump applications.

B. Part Number: 

The part and serial numbers are located on the 

wrench flat. Check the part number on the product label and confirm 
which of the below model configurations you have purchased:
Part Number 

Range 

Supply 

Mount

XP88-0 

24.6’ (7.5 m) 

18-28 VDC 

2” NPT

XP89-0 

32.8’ (10 m) 

18-28 VDC 

2” NPT

About this Manual: 

PLEASE READ THE ENTIRE MANUAL 

PRIOR  TO  INSTALLING  OR  USING  THIS  PRODUCT.    This 
manual  includes  information  on  the  XP8_-0  Ultrasonic  Level 
Transmitter  from  FLOWLINE.  Please  refer  to  the  part  number 
located on the transmitter label to verify the exact model configura-
tion which you have purchased.

User’s Responsibility for Safety: 

FLOWLINE manufac-

tures a broad range of level sensing technologies. While each of 
these sensors is designed to operate in a wide variety of applica-
tions, it is the user’s responsibility to select a sensor model that is 
appropriate for the application, install it properly, perform tests of 
the installed system, and maintain all components. The failure to do 
so could result in property damage or serious injury. 

Proper Installation and Handling: 

Only properly trained 

staff  should  install  and/or  repair  this  product.  Never  overtighten 
the transmitter within the fitting. Always check for leaks prior to 
system start-up.

Opening  The  Enclosure: 

EchoSafe  is  designed  to  be 

installed in a hazardous areas and, when installed, do not open 
the unit while power is applied. Always disconnect the power 
source from EchoSafe prior to opening, programming, install-
ing, or removing it. Additionally, ensure that electrical wiring, 
fittings and mechanical connections conform to all applicable 
electrical codes.
 

Material Compatibility: 

The XP8_ series enclosure is made 

of a Aluminum.  The transducer is made of Polyvinylidene Fluoride 
(PVDF).    Make  sure  that  the  model  which  you  have  selected  is 
chemically compatible with the application media and it’s environ-
ment.

Enclosure: 

While the transmitter housing is liquid-resistant the 

XP8_ series is not designed to be operational when immersed. It 
should be mounted in such a way that the enclosure and transducer 
do not come into contact with the application media under normal 
operational conditions.

Make  a  Fail-Safe  System: 

Design a fail-safe system that 

accommodates the possibility of transmitter and/or power failure. 
FLOWLINE  recommends  the  use  of  redundant  backup  systems 
and alarms in addition to the primary system.

Handling Static-Sensitive Circuits/Devices

When handling the transmitter, the technician should follow 

these guidelines to reduce any possible electrostatic charge 

build-up on the technicians body and the electronic part.

1.  Always touch a known good ground source before handling the 

part.  This should be repeated while handling the part and more 

frequently  after  sitting  down  from  a  standing  position,  sliding 

across the seat or walking a distance.

2.  Avoid touching electrical terminals of the part unless making connections.

Summary of Contents for EchoSafe XP88

Page 1: ...duct returned to Flowline where a There is evidence of a potentially hazardous material present with product b The product has remained unclaimed at Flowline for longer than 30 days after dutifully requesting disposition of the product THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE OF THIS WARRANTY This warranty and the obligations and liabilities of Flowline under it are ...

Page 2: ...lay type Display units Memory Supply voltage Loop resistance Signal output Signal invert Calibration Fail safe Process Temp Temp comp Electronics temp Pressure Enclosure rating Enclosure mat Window mat Transducer mat Process mount Conduit entrance Compliance Classification Approvals XP88 8 to 24 6 20 cm to 7 5 m XP89 8 to 32 8 20 cm to 10 m 0 2 of max range 0 079 2 mm 3 7 6 cm dia XP88 8 20 cm XP9...

Page 3: ...hin the fitting Always check for leaks prior to system start up Opening The Enclosure EchoSafe is designed to be installed in a hazardous areas and when installed do not open the unit while power is applied Always disconnect the power source from EchoSafe prior to opening programming install ing or removing it Additionally ensure that electrical wiring fittings and mechanical connections conform t...

Page 4: ...ammed FULL set point C EMPTY Level has reached the programmed EMPTY set point D UNITS Selectable in inches centimeters feet meter or percent The factory default is Inches E INCHES Inch units of measurement F CM Centimeters units of measurement G FEET Feet units of measurement H METERS Meter units of measurement I PERCNT 0 100 units of measurement Percent is the calcu lated value based on the 4mA a...

Page 5: ...olding down the SELECT FAST button while pressing the UP or DOWN button will increase the speed of the display Step Seven PROGRAMMING A Introduction The transmitter has two modes RUN and MENU In the RUN mode the transmitter is operational and the dis play will indicate the liquid height in inches centimeters or percent In the MENU mode the display will indicate the selected mode of calibration The...

Page 6: ...g UNITS To change UNITS from INCHES to CM or PERCENT 1 Press the SELECT FAST button and hold it for 5 seconds until MENU appears 2 When UNITS appears press the SELECT FAST button The dis play will rotate between INCHES CM FT M PERCENT and DISPLAY 3 Press the SELECT FAST button when the UNITS you want INCHES CM FT M or PERCENT appear The display will then display SAVED You have successfully changed...

Page 7: ...e to the HEIGHT value will result in an equal increase to the FILL H value A decrease to the HEIGHT value will result in an equal decrease to the FILL H value Step Eleven PROGRAMMING EchoSafe EchoSafe 4 mA 20 mA 20 mA 4 mA SELECT FAST SELECT FAST SELECT FAST 0HQX 7 EchoSafe 20 mA 4 mA Normal mA Mode 4 mA set at empty tank and 20 mA set at full tank Reverse mA Mode 20 mA set at empty tank and 4 mA ...

Page 8: ...Do not install within 3 of tank side wall Do not install with objects in the beam Do not install in applications with vacuum EchoSafe Dead Band Ventilation Hole Operational Range Highest Liquid Level Lowest Liquid Level 3 Minimum Diameter EchoSafe Warning Flowline Ultrasonic transmitters have been optimized for use in non metallic fittings For best performance avoid the use of metal fittings Insta...

Page 9: ...T FAST SELECT FAST SELECT FAST 0 18 7 7 TROUBLESHOOTING Transmitter XP88 0 XP89 0 4 mA Setting 26 4 7 5m 32 8 10m 20 mA Setting 8 20 cm 12 30 cm Factory Set Points Power Supply Power Supply 20 mA 4 mA mA 4 5 6 mA 19 20 21 Black Red EchoSafe EchoSafe Black Red TROUBLESHOOTING A Viewing Programmed VALUES 1 Press the SELECT FAST button and hold it for 5 seconds until MENU appears 2 When HELP appears ...

Reviews: