DataView™ LI55 Level Controller
Quick Start
4
| P a g e
Installing the DataView™
For most users, installation can be done without opening the case. It will
only require opening when changing from a mA to voltage configuration
(refer to the full manual found on-line at
www.flowline.com
).
When unpacking the Dataview, thoroughly inspect the unit for any
damage that may have occurred during shipping. Be sure to report any
damage, as well as any missing parts or malfunctions to your supplier or
Flowline.
Mounting the Panel
When mounting the panel, first prepare a standard 1/8 DIN panel
cutout – 3.622" x 1.772" (92 mm x 45 mm), as shown below.
Allow at least 6.0" (152 mm) clearance behind the panel for wiring.
Be sure to maintain a minimum panel thickness of 0.04" - 0.25"
(1.0 mm - 6.4 mm) to maintain Type 4X rating. This would equal
0.06" (1.5 mm) for a steel panel and 0.16" (4.1 mm) plastic panel.
Remove the DataView's two mounting brackets. Back-off the two
screws so that there is ¼" (6.4 mm) or less through the bracket. Slide
the bracket toward the front of the case and remove.
Insert the DataView into the panel cutout.
Install mounting brackets and tighten the screws against the panel.
To achieve a proper seal, tighten the mounting bracket screws
evenly until meter is snug to the panel along its short side.
DO NOT
OVER TIGHTEN
, as the rear of the panel may be damaged.
Panel
Gasket
Mounting
Bracket
Mounting
Screw
Removable
Connectors
DataView Panel Cutout 1/8 DIN
DataView Mounting Specs
3.622" (92 mm)
1.772"
(45mm)
Panel Cutout
to DIN 43700
Square Corners to 0.060"
(1.5mm) Max Radius
A
B
Tolerances:
A: +0.032 (+0.8mm)
-0.000 (-0.0mm)
B: +0.024 (+0.6mm)
-0.000 (-0.0mm)