QUICK SETUP AND PROGRAMMING 
 

This section will take you through the key steps in setting up and programming the Loop-Powered Meter: 

A.  Confirm the Operational Scale for the Application 

B.  Select the Decimal Point location 

C.  Select the Units of Operation 

D.  SCALE the 4-20mA Input 

E.  Adjust the Bar Graph 

 
SETTING NUMERIC VALUES 

The numeric values are set using the 

RIGHT Arrow 

and 

UP Arrow

 buttons. Press 

RIGHT Arrow

 to select 

next digit and 

UP Arrow

 to increment digit value. The selected digit will flash.  

Press and hold 

UP Arrow

 to auto-increment the display value. If you have made a mistake or would like to 

enter a new value, select the left-most digit and press and hold the 

RIGHT Arrow

 button until all digits reset to 

zero. 

Press the 

ENTER

 button at any time to accept a setting or 

MENU

 button to exit without saving changes. 

Note:

 the underscore in the graphic below is provided to show which digit would be flashing. 

 

 

A.  Confirm the Operation Scale for the Application 

Typically, the LI24 series must match the operational span of the transmitter mounted on top of or 
inside the tank.  The operational span is the 4-20mA span of the transmitter.  Ideally, the transmitter will 
locate 4mA at the bottom of the tank and the 20mA will be at some known level near the top of the tank 
(see below).  When using Flowline level transmitters, the Sensor Height setting will place 4mA at the 
bottom or Zero level.  The 20mA will be the Fill-Height setting.  

  

 

Confirm what number you want the LI24 series to display when the tank is empty (4mA) and 
when the tank is full (20mA).  

 

 

 
 

 

Summary of Contents for DataLoop LI24 Series

Page 1: ...Hu 19 Flowline Rights Reser e in USA 24 Series Data Loop Pow umbolt Street Los Inc rved s Quick S aLoo wered Met Alamitos CA 9072 IEC Start op ters 20 p 562 598 3015 CEx 5 f 562 431 8507 w flowline co...

Page 2: ...s Area Bar graph Two Solid State Relays PD6608 L5N FL LI24 1211 Loop Powered Hazardous Area Bar graph Two Solid State Relays and 4 20mA Analog Output Manufactured by Precision Digital Corporation 233...

Page 3: ...ition Safety requirements for electrical equipment for measurement control and laboratory use Additional Standards UL 50E HAZARDOUS AREA APPROVALS ATEX Certificate Number CML 17ATEX2015X 0518 Ex ia II...

Page 4: ...2 or Zone location if so approved Under certain extreme circumstances the non metallic parts incorporated in the enclosure of this equipment may generate an ignition capable level of electrostatic cha...

Page 5: ...ion installation instructions for associated apparatus barrier must be followed when installing this equipment For safe installation of an ATEX approved transmitter in series with LI24 loop powered me...

Page 6: ...clearance behind the panel for wiring Be sure to maintain a minimum panel thickness of 0 04 0 25 1 0 mm 6 4 mm to maintain type 4X rating This would equal 0 06 1 5 mm for a steel panel and 0 16 4 1 mm...

Page 7: ...light is recommended for dim lighting conditions and is enabled when wired as shown in the following diagram The backlight may be bypassed if installed in bright lighting conditions to reduce the maxi...

Page 8: ...value of a digit or character ENTER F3 Use this button to access a menu or to accept a setting or programmed digit character value PROGRAMMING THE LOOP POWERED METER To enter the LI24 series Programm...

Page 9: ...ess and hold the RIGHT Arrow button until all digits reset to zero Press the ENTER button at any time to accept a setting or MENU button to exit without saving changes Note the underscore in the graph...

Page 10: ...ace The accuracy is very good but may not be practical When selecting a decimal point take into account the practical scale for reading the level of liquid To set the Decimal Point 1 Press the MENU bu...

Page 11: ...s feet cm meter etc Please determine the units of operation that you want to appear on the display To set the Units of Operation 1 Press MENU button to bring up the SETUP Input screen 2 Press ENTER bu...

Page 12: ...inputs and corresponding display value In the examples above the 4 mA Empty reading could represent 0 Gallons 0 Feet 0 Inches or 0 0 The 20 mA Full reading could represent 5 000 Gallons 10 00 Feet 12...

Page 13: ...efault is 00100 00 and typically be the value you want to display when the tank is full b To change the value use the UP Arrow to incrementally increase the selected digit and the Right Arrow to move...

Page 14: ...This feature can be enabled or disabled using the Bargraph menu BARGRAPH The value displayed on the bar graph can be the percentage of full scale PV PCT or the percentage of a user programmable range...

Page 15: ...LIN6606QS_FL_A 02 19 QS302110A 15 This Page Intentionally Left Blank...

Page 16: ...s for which the original purchaser does not follow the warranty procedures outlined above 2 have been subjected to electrical mechanical or chemical damage due to improper accidental or negligent use...

Reviews: