
|
4
LIN6606QS_FL_A 02/19
QS302110A
ATEX/IECEx SPECIAL CONDITIONS FOR SAFE USE
The following conditions relate to safe installation and/or use of the equipment.
•
The permitted ambient temperature range for the LI24 is -40°C to 70°C.
•
The equipment must be installed in an enclosure which provides a minimum degree of protection of
IP20 for the equipment connections.
•
Under certain extreme circumstances, the non-metallic parts incorporated in the enclosure of this
equipment may generate an ignition-capable level of electrostatic charge. Therefore, the equipment
shall not be installed in a location where the external conditions are conducive to the build-up of
electrostatic charge on such surfaces. This is particularly important if the equipment is installed in a
zone 0 location. In addition, the equipment shall only be cleaned with a damp cloth.
•
The equipment loop/power port must be connected to an intrinsically safe barrier with U
o
≥ 11V.
•
Entity parameters must meet the following requirements:
U
i
: 30 V; I
i
: 175 mA; C
i
: 0 μF; L
i
: 0 μH; P
i
: 1.0 W
•
For ATEX Certification, barrier and transmitter must be ATEX Certified with Entity Parameters and must
be connected per manufacturer’s instructions.
FOR EUROPEAN COMMUNITY:
The LI24 must be installed in accordance with the Essential Health & Safety Requirements of Directive
2014/34/EU, the product certificates CML 17ATEX2015X and IECEx CML 17.0008X, and the product manual.
UL/C-UL SPECIAL CONDITIONS FOR SAFE USE
•
Associated apparatus may be in a Division 2 or Zone location if so approved.
•
Under certain extreme circumstances, the non-metallic parts incorporated in the enclosure of this
equipment may generate an ignition-capable level of electrostatic charge. Therefore the equipment
shall not be installed in a location where the external conditions are conducive to the build-up of
electrostatic charge on such surfaces. This is particularly important if the equipment is installed in a
zone 0 location. In addition, the equipment shall only be cleaned with a damp cloth.
•
The equipment shall be installed in a tool secured enclosure which provides a minimum degree of
protection of IP20 for the equipment connections.
•
Entity parameters must meet the following requirements:
U
i
: 30 V; I
i
: 175 mA; C
i
: 0 μF; L
i
: 0 μH; P
i
: 1.0 W
I.S. Equipment Entity
Parameters
Required Relationship
Between Entity Parameters
I.S. Barrier Entity
Parameters
V
max
(or U
i
)
≥
V
oc
or V
t
(or U
o
)
I
max
(or I
i
)
≥
I
s
c or I
t
(or I
o
)
P
max
, P
i
≥
P
o
C
i
+ C
cable
≤
C
a
(or C
o
)
L
i
+ L
cable
≤
L
a
(or L
o
)
For Division 2 and Zone 2 Applications:
Division 2 and Zone 2 installations do NOT require the use
of an intrinsically-safe barrier or intrinsically-safe entity parameters. Class I, Division 2, Groups A, B, C,
and D T4 and Class I, Zone 2, Group IIC T4, -40C <= Ta <= +70C. Ratings: V = 30 V dc, I = 30 mA;
Relay Ratings: 250V ac/dc 1A
FOR NORTH AMERICAN COMMUNITY:
Installation and service of this device and/or associated apparatus (barrier) should be performed only by
trained service personnel and must be installed in accordance with the manufacturer’s control drawing, Article
504 of the National Electric Code (ANSI/NFPA 70) for installation in the United States, or Section 18 of the
Canadian Electrical Code for installations in Canada.