FlowLine DataLoop LI24 Series Quick Start Manual Download Page 12

 

|

   12

 

LIN6606QS_FL_A  02/19

 

QS302110A

 

D.  SCALE THE 4-20MA INPUT 

 
The 4-20 mA input can be scaled to the appropriate values for a given application. The 4-mA input 
(input 1) should have a corresponding display value (display 1) which represents the low end of the 
process value range being measured by the transmitter. Likewise, the 20-mA input (input 2) should 
have a display value (display 2) which represents the high end of the process value range. 
 

 

Input 

Display 

Input Example 

Display Example 

Typically 04.000 mA 

Value of tank at Empty 

04.000 

0000.0 

Typically 20.000 mA 

Value of tank at Full 

20.000 

0100.0 

 

For example:

 If the meter is used to display the level of a 100 ft tall tank, the transmitter should send a  

4 mA signal when the tank is empty and a 20-mA signal when the tank is full. The meter should be 
programmed to interpret these inputs on a display range of 0-100, so that at 4-mA the meter will display 
0 and at 20-mA the meter will display 100. 
 
A signal source is not needed to scale the meter; simply program the inputs and corresponding display 
value 
 

 

 
In the examples above, the 4 mA/Empty reading could represent 0 Gallons, 0 Feet, 0 Inches or 0.0%. 
The 20 mA/Full reading could represent 5,000 Gallons, 10.00 Feet, 120.0 Inches or 100.0%.  Setting 
4mA for an empty tank and 20 mA for a full tank simplifies configuration. 

 

To set the SCALE function: 

1)  Press 

MENU

 button to bring up the SETUP/Input screen. 

2)  Press 

ENTER

 button to bring up SCALE/Units screen. 

3)  Press 

Right Arrow

 button to bring up SCALE/Input_1 screen. 

4)  Press 

ENTER

 button to bring up INP 1/04.000 screen. 

a.  This is the default of 04.000mA and does not need to be changed. 
b.  If the value needs to changed, use the 

UP Arrow

 to incrementally increase the selected digit and the 

Right Arro

w to move to the next digit.  

5)  Press 

ENTER

 to save the Input 1 setting and to bring up SCALE/Disp_1 screen.  

6)  Press 

ENTER

 to bring up DSP_1/00000000 screen. 

a.  The default is 0000000 and typically does not need to be changed. 
b.  If the value needs to changed, use the 

UP Arrow

 to incrementally increase the selected digit and the 

Right Arro

w to move to the next digit.  

7)  Press 

ENTER

 to save the Display 1 setting and to bring up SCALE/Input_2 screen. 

8)  Press 

ENTER

 to bring up INP_2/20000 screen.   

Summary of Contents for DataLoop LI24 Series

Page 1: ...Hu 19 Flowline Rights Reser e in USA 24 Series Data Loop Pow umbolt Street Los Inc rved s Quick S aLoo wered Met Alamitos CA 9072 IEC Start op ters 20 p 562 598 3015 CEx 5 f 562 431 8507 w flowline co...

Page 2: ...s Area Bar graph Two Solid State Relays PD6608 L5N FL LI24 1211 Loop Powered Hazardous Area Bar graph Two Solid State Relays and 4 20mA Analog Output Manufactured by Precision Digital Corporation 233...

Page 3: ...ition Safety requirements for electrical equipment for measurement control and laboratory use Additional Standards UL 50E HAZARDOUS AREA APPROVALS ATEX Certificate Number CML 17ATEX2015X 0518 Ex ia II...

Page 4: ...2 or Zone location if so approved Under certain extreme circumstances the non metallic parts incorporated in the enclosure of this equipment may generate an ignition capable level of electrostatic cha...

Page 5: ...ion installation instructions for associated apparatus barrier must be followed when installing this equipment For safe installation of an ATEX approved transmitter in series with LI24 loop powered me...

Page 6: ...clearance behind the panel for wiring Be sure to maintain a minimum panel thickness of 0 04 0 25 1 0 mm 6 4 mm to maintain type 4X rating This would equal 0 06 1 5 mm for a steel panel and 0 16 4 1 mm...

Page 7: ...light is recommended for dim lighting conditions and is enabled when wired as shown in the following diagram The backlight may be bypassed if installed in bright lighting conditions to reduce the maxi...

Page 8: ...value of a digit or character ENTER F3 Use this button to access a menu or to accept a setting or programmed digit character value PROGRAMMING THE LOOP POWERED METER To enter the LI24 series Programm...

Page 9: ...ess and hold the RIGHT Arrow button until all digits reset to zero Press the ENTER button at any time to accept a setting or MENU button to exit without saving changes Note the underscore in the graph...

Page 10: ...ace The accuracy is very good but may not be practical When selecting a decimal point take into account the practical scale for reading the level of liquid To set the Decimal Point 1 Press the MENU bu...

Page 11: ...s feet cm meter etc Please determine the units of operation that you want to appear on the display To set the Units of Operation 1 Press MENU button to bring up the SETUP Input screen 2 Press ENTER bu...

Page 12: ...inputs and corresponding display value In the examples above the 4 mA Empty reading could represent 0 Gallons 0 Feet 0 Inches or 0 0 The 20 mA Full reading could represent 5 000 Gallons 10 00 Feet 12...

Page 13: ...efault is 00100 00 and typically be the value you want to display when the tank is full b To change the value use the UP Arrow to incrementally increase the selected digit and the Right Arrow to move...

Page 14: ...This feature can be enabled or disabled using the Bargraph menu BARGRAPH The value displayed on the bar graph can be the percentage of full scale PV PCT or the percentage of a user programmable range...

Page 15: ...LIN6606QS_FL_A 02 19 QS302110A 15 This Page Intentionally Left Blank...

Page 16: ...s for which the original purchaser does not follow the warranty procedures outlined above 2 have been subjected to electrical mechanical or chemical damage due to improper accidental or negligent use...

Reviews: