Step Display
Description
Values
6
Select minimum control value.
*scrolling top:
SET MINIMUM LIMIT
Volt default: 2.
Options: leave at default: 2.
7
Select maximum control value.
*scrolling top:
SET MAXIMUM LIMIT
Volt default: 10.
Options: leave at default: 10.
8
Select feedback signal.
*scrolling top:
SELECT FEEDBAC SIGNAL
Default: AU; Automatic match of
control signal if analog.
Options: leave at default: All,
or choose 2-10V DC
9
Set the designed maximum flow.
Accuracy: Greatest of either ±5% of
controlled flow or ±2% of max. valve flow.
*scrolling top:
SELECT MAXIMUM FLOW
Default: Maximum setting.
Values depend on valve model and unit
scale chosen in step 2 and 3.
Stepping increments as per tech note.
10
Select direction of rotation.
*scrolling top:
SELECT ROTAT DIRECT
Default: Normally Closed (NC).
Options: leave at default: Normally
Closed (NC).
11
Activation of password.
*scrolling top:
ACTIVAT PASS WORD
Default: Disable.
Options: Enable or Disable.
If Enabled password is required to ac-
cess alarm and programming menu.
12
Select direction of rotation when Failsafe.
*scrolling top:
SELECT FAIL SAFE DIRECT
Default: Closed.
Options: Open or Closed.
Only valid for SM.0.0.0.4 (failsafe
model). Failsafe direction open means
opening to max. flow
chosen in step 9.
Failsafe mode (only SM.0.0.0.4)
If power supply is out of range or lost, failsafe mode will be activated:
1. Approx. 80 sec. delay.
2. Actuator opens/closes valve (according to step 12 in programming menu).
3. Actuator shuts off.
If power supply is restored during action 1. or 2., failsafe mode is deactivated.
FlowCon FIT 65-250 mm (2 1/2”-10”)