P1
P2
Black
Red
FlowCon Intelligent Interface
Black
Green
White
Red
White
Green
Red (no function)
White/Black - Ground/common
Red - Power 24V DC
FlowCon Pressure Sensors
FlowCon Temperature Sensors
Black
Red
FlowCon Intelligent Interface
White
Green
Red (no function)
Black
Green
White
Red
White/Yellow - Input 0-5VDC
Black - Ground/common
Red - Power 24V DC
T1
T2
Start-Up Sequence
When power is turned on, the actuator will auto-
matically calibrate to determine closing point of
the valve. Calibration can take up to 10 minutes
depending on the valve’s position at start-up.
During calibration actuator display will show
“
CAL
”. Hereafter it will procced to normal opera-
tion mode (according to control signal).
If no control signal is detected, flush is started if
enabled in the programming menu (enabled by
default), opening the valve to 5/6 of fully open.
Actuator display will show “
FLUSH
” until control
signal is detected.
At first start-up please enter programming menu
to set actuator settings.
FlowCon FIT 65-250 mm (2 1/2”-10”)
1B95095 - 02/2020
This paper is a supplement to the
FlowCon General Instruction
Latest release of any FlowCon material is available on
Page 5 of 10