Intelligent Interface Connection
The FlowCon Energy FIT System includes the
state-of-the-art FlowCon Intelligent Interface
which is the controller in the FIT System. The
Intelligent Interface is compatible with 24V DC
only.
Sensor Kit Connection
The FlowCon Energy FIT System includes two
temperature sensors that should be installed as
close to the coil as possible, within 0.3-3 mtr (1-
10 ft) if possible. T1 should be installed on the
inlet to the coil and T2 on the outlet of the coil.
Sensors are to be installed in 1/4” ISO ports.
The temperature sensor cable (3 mtr / 9.8 ft) at-
taches - via quick-connectors - to the Intelligent
Interface cable (0.6 mtr / 2 ft).
In addition, the FIT System includes two pres-
sure sensors that must be installed on or close
to the PICV valve. P1 should be installed on the
inlet of the PICV and P2 on the outlet. Sensors
are to be installed in 1/4” ISO ports. The pres-
sure sensor cable (1.6 mtr / 6 ft) attaches - via
quick-connectors - to the Intelligent Interface
cable (0.6 mtr / 2 ft).
Be aware to connect according to wiring diagrams
page 4 and 5 to avoid loosing warranty.
FlowCon App
Download the FlowCon App from AppStore or
GooglePlay and take full advantage of the FIT
system. Information on
ΔT, ΔP, flow and BTU is
transferred.
FlowCon FIT 65-250 mm (2 1/2”-10”)
1B95095 - 02/2020
This paper is a supplement to the
FlowCon General Instruction
Latest release of any FlowCon material is available on
Page 3 of 10