![FlowCon SM.3 Installation And Operation Instruction Manual Download Page 6](http://html1.mh-extra.com/html/flowcon/sm-3/sm-3_installation-and-operation-instruction-manual_2308047006.webp)
*
*
*
*
*
*
Step Display
Description
Values
0
Password.
*scrolling top:
ENTER PASS WORD
Disabled by default
Password: 3569266.
Only if Enabled (in step 11).
Change one digit at a time, press
and
to move between digits.
At last digit, press
to go to next step.
1
Select language.
*scrolling top:
SELECT LANGUAG
Default: English.
Possibility to choose other languages later
on (not currently an option).
2
Select valve model onto which the
actuator is installed.
*scrolling top:
SELECT VALVE MODEL
Default: SM.0.0.
Select from the 9 available valve models,
starting from SM.3.0.
Options: SM.3.0, SM.3.1...
3
Choose unit scale for flow rate.
*scrolling top:
SELECT UNIT SCALE
Default: l/sec.
Options: l/sec or l/hr or GPM.
4
Activate Flush mode at start-up.
*scrolling top:
SELECT FLUSH MODE
Default: Enable.
Options: Enable or Disable.
When no control signal (analog) is detected
at start up, flush mode is started (5/6 of fully
opened). It will be dismissed when control
signal is detected.
5
Select type of control signal.
*scrolling top:
SELECT CONTROL SIGNAL
Default: 2-10VDC.
Options: 2-10VDC or 4-20mA or digital.
Choose:
• 2-10VDC for VDC
All values selected in the programming menu are stored in non-volatile memory.
Programming Menu
The programming menu is always accessible. To enter the program-
ming menu,
simultaneously press
and
for 6 seconds,
until
bottom line in display blinks.
To change a value, press
or
. For quick scroll through values
hold down
or
. Press
to accept a value and go to next step
and press
to go to previous step.
For fast menu exit press
and
simultaneously for 6 seconds. The
actuator will automatically return to normal operation mode if no ac-
tion is detected on arrow keys for 1 minute.
This paper is a supplement to the
FlowCon General Instruction
Latest release of any FlowCon material is available on
FlowCon FIT 65-250 mm (2 1/2”-10”)
1B95095 - 02/2020
Page 6 of 10