background image

FAA-28, Technical Manual, Rev.1.1.0 

February 2022 

 

 

Page 16 of 21 

5.  Setpoints 

5.1 

Setpoint Connection 

FAA-28 has 2 free relay contact output. These outputs can be connected to 
maximum 230VAC or maximum 30VDC, maximum 1A loads. Reverse diode 
connection to the DC loads is recommended to increase the relay contact life and to 
reduce the disturbances. Outputs connection is; 
 

 

 

5.2 

Setpoint Adjustment 

The instrument closes the relay contacts if the weight value is higher than the 
adjusted setpoint. These contact signals can be used to stop charging or discharging 
or produce alarm signal. You can apply two methods to adjust setpoints. 

5.3 

Adjustment to the Load on the Scale 

Setpoint can be adjusted to the load value on the scale: 

  Load the scale to the value you want to produce setpoint signal 

  Turn the programming switch to 

S1

 (or 

S2

) position from operation position  

(from 

V

 or 

I

 position) 

  Turn the Adj. switch to positions  

  position and turn it back to 

0

 - position  

2 seconds later 

  Turn the programming switch to analog output type position for operation 

mode (

V

 or 

I

 position) or to other setpoint position to adjust it 

5.4 

Adjustment by Measuring the Analog Output 

You can adjust the setpoint by measuring the analogue output value without loading 
the scale: 

  Connect the measuring instrument to the analog output. 

  Turn the programming switch to 

S1

 (or 

S2

) position from operation position  

(from 

V

 or 

I

 position). 

  Increase or decrease the analog output by adjustment rotary switch (refer to 

table in 

chapter 5.1

 ). 

Do not bring the adjustment switch position to  

 position in this adjustment. 

The adjustment switch must be at 

0

 - position at the end of the adjustment. 

   Turn the programming switch to analog output type position to start operation 

(

V

 or 

I

 position) or to other setpoint position to adjust it. 

 

Summary of Contents for FAA-28

Page 1: ...FAA 28 Analog Amplifier Technical Manual Flintec GmbH Bemannsbruch 9 74909 Meckesheim GERMANY www flintec com...

Page 2: ...sioning 9 4 Adjustments 10 4 1 Adjustment with Rotary Switches 10 4 2 Fast Adjustment to Nominal Output Range 12 4 3 eCal Electronic Adjustment Via xFace Software 12 4 4 Adjustment eCal With PLC 13 4...

Page 3: ...this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means mechanical photocopying recording or otherwise without the prior written permission of Flint...

Page 4: ...t the electronic calibration eCal and fast calibration with 20 max test load reduces the calibration time All analog outputs of the instruments are matched in the production to perform calibration at...

Page 5: ...to chapter 9 Features Minimized zero and span drifts due to its microcontroller technology and high accuracy very low temperature drift 24 bits ADC and 16 bits DAC converters Long time stability and l...

Page 6: ...PC Preadjusted instrument for calibration at PLC Digital Filter Programmable 9 step adjustable digital adaptive filter Analogue outputs Current output for 0 20 mA and 4 20 mA or voltage output for 0 5...

Page 7: ...nst radio frequency interference and the cabinet shall be connected to ground against the electromagnetic disturbances Load cell cable and analog output cable trays must be separated from others if po...

Page 8: ...rgizing to avoid damages of the instrument and load cells In 4 wire installations the sense and excitation pins with the same polarity should be short circuited at the connector side If you have junct...

Page 9: ...one of the analog output types can be used at the same time and has to be selected in the setup type Install the analog output measuring instrument for adjustment e g multimeter Pin Name Definition I...

Page 10: ...osition Connect or disconnect TxD and RxD pins according the table above to set the output range Turn the adjustment switch to the position After 2 seconds turn in back to the 0 position if the instru...

Page 11: ...flashes to indicate the instrument is not in operation mode Zero Adjustment Connect the measurement instrument Multimeter is recommended to the analog output Unload the scale the scale must be empty...

Page 12: ...2 5VDC Turn the adjustment switch to the G position from the analog output type position you set before Increase or decrease the analog output by adjustment rotary switch to the calculated output val...

Page 13: ...n and turn it back to 0 position 2 seconds later Turn the programming switch to analog output type position for operation For example for 4 20mA range and for 100kg capacity scale load the scale 20kg...

Page 14: ...RS232C serial interface by commands or by xFace software If you want to use your own software to calibrate the FAA 28 from your PLC or PC you may use the commands below The yellow colored bytes are th...

Page 15: ...01100009000204000000FAE6 Scale capacity is 250kg Response 011000090002E4 ACK Step 6 SAVE with estimated dead load value Command 011000000001020007E5 Save the eCal values Response 011000000001EE ACK Or...

Page 16: ...e_Add Function Last_data STX and CSUM are neglected while calculating CSUM Example For Medium 1 filter 011000220001020001XX CSUM 0 01 10 00 22 00 01 02 00 01 0 37 C9 Command is 011000220001020001C9 Ca...

Page 17: ...n the programming switch to S1 or S2 position from operation position from V or I position Turn the Adj switch to positions position and turn it back to 0 position 2 seconds later Turn the programming...

Page 18: ...ted Off 0 10VDC Open circuited Flash 0 5VDC Short circuited Blinking The status of the LEDs in the operation type is given in the table below Refer to chapter 9 in case of the Err LED turns on The ana...

Page 19: ...ntains the xFace software v2 03 or higher into the CD ROM drive Double click Setup exe to start the installation The setup Wizard will be displayed Follow the menus in the setup wizard step by step Af...

Page 20: ...oints in section Setup 9 In section Status instrument information are available 10 Power off the instrument before disconnecting from PC Bring the programming switch to the analog output type position...

Page 21: ...not let unauthorized people interfere with the instrument FRONT PANEL LEDS DEFINITION Run V I Err Off Off Off No power Board failure On On Off Operation in 4 20mA output type On Off Off Operation in...

Page 22: ...FAA 28 Technical Manual Rev 1 1 0 February 2022 Page 21 of 21 Flintec GmbH Bemannsbruch 9 74909 Meckesheim GERMANY www flintec com...

Reviews: