FAA-28, Technical Manual, Rev.1.1.0 

February 2022 

 

 

Page 13 of 21 

4.4 

Adjustment (eCal) With PLC 

All instruments are adjusted in the production to operate in its analog output range 
between 0mV and 10mV load cell signal as default. For example, if the instrument is 
at factory default values and programmed to operate 4 

– 20mA output range, the 

output will be 4mA at 0mV and 20mA at 10mV load cell signal (only for 2mV/V load 
cells).  
 
Changing the FAA-28 instrument a recalibration is not required due to matching 
instruments in production by Flintec. 

 

Warning:

 If the instrument was adjusted before and its factory defaults are changed, 

you should load factory defaults with xFace. 
 

FAA-28 Programming via RS232C  

 

FAA-28 can be electronically calibrated via RS232C serial interface by commands or 
by xFace software. If you want to use your own software to calibrate the FAA-28 from 
your PLC or PC, you may use the commands below. The yellow colored bytes are 
the data in the command and blue colored bytes are check sum in this document. 
 
Output type setting and eCal electronic calibration should be done in sequence.  

 
RS232C PORT SETTING : 

Adjust your PC or PLC serial port as 9600, 8 None 1.  
 

DATA STRUCTURE :

   

ASCII, HEX DATA and CR (Carriage Return) at the end of the command. 

 
COMMANDS:  

 

 

 

 

 

Descriptions 

 

1. Analog output type setting: 
 

a)  4 - 20mA setting: 

Command: 

@01100000000102000BE1   

Set to 4-20 mA range 

Response: 

@011000000001EE   

 

 

ACK 

 

b)  0 - 20mA setting: 

Command: 

@011000000001020014D8   

Set to 0-20 mA range 

Response 

@011000000001EE   

 

 

ACK 

 

c)  0 - 10VDC setting :

 

 

Command: 

@01100000000102000AE2   

Set to 0-10 VDC range 

Response 

@011000000001EE   

 

 

ACK 

 

d)  0 - 5VDC setting :

 

 

 

Command: 

@011000000001020013D9   

Set to 0-5 VDC range 

Response 

@011000000001EE   

 

 

ACK 

 

Summary of Contents for FAA-28

Page 1: ...FAA 28 Analog Amplifier Technical Manual Flintec GmbH Bemannsbruch 9 74909 Meckesheim GERMANY www flintec com...

Page 2: ...sioning 9 4 Adjustments 10 4 1 Adjustment with Rotary Switches 10 4 2 Fast Adjustment to Nominal Output Range 12 4 3 eCal Electronic Adjustment Via xFace Software 12 4 4 Adjustment eCal With PLC 13 4...

Page 3: ...this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means mechanical photocopying recording or otherwise without the prior written permission of Flint...

Page 4: ...t the electronic calibration eCal and fast calibration with 20 max test load reduces the calibration time All analog outputs of the instruments are matched in the production to perform calibration at...

Page 5: ...to chapter 9 Features Minimized zero and span drifts due to its microcontroller technology and high accuracy very low temperature drift 24 bits ADC and 16 bits DAC converters Long time stability and l...

Page 6: ...PC Preadjusted instrument for calibration at PLC Digital Filter Programmable 9 step adjustable digital adaptive filter Analogue outputs Current output for 0 20 mA and 4 20 mA or voltage output for 0 5...

Page 7: ...nst radio frequency interference and the cabinet shall be connected to ground against the electromagnetic disturbances Load cell cable and analog output cable trays must be separated from others if po...

Page 8: ...rgizing to avoid damages of the instrument and load cells In 4 wire installations the sense and excitation pins with the same polarity should be short circuited at the connector side If you have junct...

Page 9: ...one of the analog output types can be used at the same time and has to be selected in the setup type Install the analog output measuring instrument for adjustment e g multimeter Pin Name Definition I...

Page 10: ...osition Connect or disconnect TxD and RxD pins according the table above to set the output range Turn the adjustment switch to the position After 2 seconds turn in back to the 0 position if the instru...

Page 11: ...flashes to indicate the instrument is not in operation mode Zero Adjustment Connect the measurement instrument Multimeter is recommended to the analog output Unload the scale the scale must be empty...

Page 12: ...2 5VDC Turn the adjustment switch to the G position from the analog output type position you set before Increase or decrease the analog output by adjustment rotary switch to the calculated output val...

Page 13: ...n and turn it back to 0 position 2 seconds later Turn the programming switch to analog output type position for operation For example for 4 20mA range and for 100kg capacity scale load the scale 20kg...

Page 14: ...RS232C serial interface by commands or by xFace software If you want to use your own software to calibrate the FAA 28 from your PLC or PC you may use the commands below The yellow colored bytes are th...

Page 15: ...01100009000204000000FAE6 Scale capacity is 250kg Response 011000090002E4 ACK Step 6 SAVE with estimated dead load value Command 011000000001020007E5 Save the eCal values Response 011000000001EE ACK Or...

Page 16: ...e_Add Function Last_data STX and CSUM are neglected while calculating CSUM Example For Medium 1 filter 011000220001020001XX CSUM 0 01 10 00 22 00 01 02 00 01 0 37 C9 Command is 011000220001020001C9 Ca...

Page 17: ...n the programming switch to S1 or S2 position from operation position from V or I position Turn the Adj switch to positions position and turn it back to 0 position 2 seconds later Turn the programming...

Page 18: ...ted Off 0 10VDC Open circuited Flash 0 5VDC Short circuited Blinking The status of the LEDs in the operation type is given in the table below Refer to chapter 9 in case of the Err LED turns on The ana...

Page 19: ...ntains the xFace software v2 03 or higher into the CD ROM drive Double click Setup exe to start the installation The setup Wizard will be displayed Follow the menus in the setup wizard step by step Af...

Page 20: ...oints in section Setup 9 In section Status instrument information are available 10 Power off the instrument before disconnecting from PC Bring the programming switch to the analog output type position...

Page 21: ...not let unauthorized people interfere with the instrument FRONT PANEL LEDS DEFINITION Run V I Err Off Off Off No power Board failure On On Off Operation in 4 20mA output type On Off Off Operation in...

Page 22: ...FAA 28 Technical Manual Rev 1 1 0 February 2022 Page 21 of 21 Flintec GmbH Bemannsbruch 9 74909 Meckesheim GERMANY www flintec com...

Reviews: