Flexit Roomie Dual Assembly And Operation Instructions Manual Download Page 24

24

R O O M I E   D U A L

8. Troubleshooting

Problem Possible 

reasons

Troubleshooting

When switching on the venti-
lator the fan does not start.

No power supply.

Make sure the power supply line is connected cor-
rectly, otherwise troubleshoot the connection error.

The motor is jammed, the impeller blades are soiled.

Turn the ventilator off. Troubleshoot the motor jam 
and the impeller clogging. Clean the blades. Restart 
the ventilator.

Circuit breaker tripping during 
the ventilator start-up.

Overcurrent as a result of short circuit in the electric 
circuit.

Turn the ventilator off. 
Contact the Seller for further information.

Low air flow.

Low set fan speed.

Set higher speed.

The filters, the fan or the regenerator are clogged.

Clean or replace the filter. Clean the fan and the heat 
exchanger.

Noise, vibration.

The impeller is clogged.

Clean the impeller.

Loose screw connection of the ventilator casing or 
the outer ventilation hood.

Tighten the screws of the ventilator or the outer 
ventilation hood.

9.  Storage and transportation regulations

Store the unit in the manufacturer’s original packing box in a 
dry closed ventilated premise with temperature range from 
+5 °C to + 40 °C.

Storage environment must not contain aggressive vapours 
and chemical mixtures provoking corrosion, insulation and 
sealing deformation.

Use suitable hoist machinery for handling and storage 
operations to prevent possible damage to the unit.

Follow the handling requirements applicable for the 
particular type of cargo.

The unit can be transported in the original packing by any 
mode of transport without limitation provided proper 
protection against precipitation and mechanical damage.

Prior to the initial power-up after 
transportation at subzero 
temperatures allow the unit to warm 
up at room temperature for at least 2 
hours.

Avoid sharp blows, scratches or rough handling during 
loading and unloading.

Do not expose the unit to sudden changes in temperature.
Such changes can lead to condensation of moisture inside 
the unit and performance disturbance when the unit is 
switched on.

Summary of Contents for Roomie Dual

Page 1: ...Roomie Dual 116027EN 05 2020 03 Assembly and Operation Instructions Heat recovery single room reversible ventilation unit ART NR 115999...

Page 2: ...2 R O O M I E D U A L...

Page 3: ...ivery set 6 3 Technical data 6 4 Product desciption 8 5 Mounting and set up 10 6 Connection to power mains and control 14 7 Technical maintenance 22 8 Troubleshooting 24 9 Storage and transportation r...

Page 4: ...physical or mental capacity or by persons with lacking experience or knowledge provided they have received instructions in the safe use of the appliance or are supervised to ensure safe use and provid...

Page 5: ...ut the installation and maintenance operations with wet hands Do not operate the unit outside the temperature range stated in the user s manual Do not operate the unit in aggressive or explosive envir...

Page 6: ...s evaporation of chemicals sticky substances brous materials coarse dust soot and oil particles or environments favourable for the formation of hazardous substances toxic substances dust pathogenic ge...

Page 7: ...h Roomie Dual 280 500 Front panel Outer ventilation hood Air duct length 235 71 285 207 85 137 138 Roomie Dual Overall dimensions of the indoor unit mm Standard duct is 500 mm which can be cut to min...

Page 8: ...objects to the ventilator Unit design Air ow separators Designed for separation of supply and exhaust air streams Outer ventilation hood Prevents ingress of water and foreign objects into the ventilat...

Page 9: ...as three operation modes Regeneration One of the fans of the ventilator operates in extract mode and the other one in supply mode The fans change their rotation direction every 70 seconds Ventilation...

Page 10: ...very The air duct end must protrude for the distance that enables installation of the outer ventilation hood 0 3 mm min 3 mm Insert the air duct into the wall as shown in the picture on the left Insta...

Page 11: ...of the master plate with respect to the horizon line it is recommended to use a builder s level Then mark the fastening holes for installation of the sup plied dowels and drill the holes to a required...

Page 12: ...e wall with the screws supplied with the mounting kit of the ventilator Insert the wires under the cable clamp and connect the socket connector to the circuit board The mark must be directed upwards R...

Page 13: ...ators in the air duct until it bumps up the cartridge Mark the last air ow separator to be ush with the air duct face remove it from the air duct and cut the exces sive part of the last air ow separat...

Page 14: ...from underneath the unit to the back Any connections in the terminal according to the wiring diagram Cable clamp Cable clamp The unit is rated for connection to single phase AC 100 240 V 50 60 Hz pow...

Page 15: ...tible with the unit When this is activated the ventilator switches to high speed The ventilators can be connected in series and in parallel with a central control by the master ventilator In case of i...

Page 16: ...L N L In Gnd Gnd Out NO1 NO2 12V Power input 100 240 V 50 60 Hz to the next ventilator Master Slave 1 Slave N Master Slave 1 Slave N N L N L In Gnd Gnd Out NO1 NO2 12V N L N L In Gnd Gnd Out NO1 NO2...

Page 17: ...llowed The switch position enables deactivation of the unit with the button on the side control panel 1 Turning the unit off is forbidden The switch position disables deactivation of the unit with the...

Page 18: ...Function 3 4 5 Humidity control is OFF 3 4 5 Humidity setpoint 40 3 4 5 Humidity setpoint 50 3 4 5 Humidity setpoint 60 3 4 5 Humidity setpoint 70 3 4 5 Humidity setpoint 80 Position Function 6 7 Tim...

Page 19: ...ce is follows low medium high speed Off Turning unit ON OFF Speed selection Regeneration mode In this mode the fans rotation direction changes to opposite every 70 seconds This operation mode enables...

Page 20: ...ir ow separator by pulling one of the side clamps Install the front part of the front panel and press it gently to close the air duct The fan turns off automatically The unit functionality is not chan...

Page 21: ...e Alarm indicator of the Master unit indicates an alarm in the network of the connected ventilation units Its blinking indicates shutdown of a speci c ventilation unit in the network In case of an eme...

Page 22: ...s Uplift it with a at screw driver of a respective size Disconnect the socket from the circuit board Do not pull the wires Use a at screwdriver to disconnect the socket UP Never remove the control boa...

Page 23: ...ct the Seller Some dust may accumulate on the heat exchanger block even in case of regular maintenance of the lters Clean the regenerator regularly to ensure its high heat recovery ef ciency Vacuum cl...

Page 24: ...n the screws of the ventilator or the outer ventilation hood 9 Storage and transportation regulations Store the unit in the manufacturer s original packing box in a dry closed ventilated premise with...

Page 25: ...er States relating to electromagnetic compatibility Producer VENTILATION SYSTEMS PrJSC 1 Mikhaila Kotzubinskogo St Kiev 01030 Ukraine Type Single room ventilators Roomie One Wi Roomie Dual Roomie Dual...

Page 26: ...26 R O O M I E D U A L...

Page 27: ...27 R O O M I E D U A L...

Page 28: ...Flexit AS Televeien 15 N 1870 rje www exit no...

Reviews: