16 Outputs (TF7-*72***-******-******a-*****-**; a = M, P, Q)
16.1 Configuration of a digital output as binary output
PIOX S72*
2022-05-15, UMPIOX_S72xV1-9EN
154
Output function test
The function of the output can now be tested.
• Connect a multimeter to the output.
• Select
Yes
to test the output. Select
No
to display the next menu item.
• Press ENTER.
• Select a list item as test value.
• Press ENTER.
• Select
Repeat
to repeat the test or
Finish
to display the next menu item.
• Press ENTER.
• Select
Yes
to test the status of the output signal. Select
No
to display the next menu item.
• Press ENTER.
• Select a list item as test value.
• Press ENTER.
Options\Channel A\Outputs\...\B1 Test signal
Options\Channel A\Outputs\...\B1 Enter test value
Tab. 16.4: Output function test – signal
list item
description
NC
• binary output is energized
• measured value has to be low ohmic
NO
• binary output is de-energized
• measured value has to be high ohmic
Options\Channel A\Outputs\...\B1 Test mea. range
Options\Channel A\Outputs\...\B1 Enter test value