6.4 Control board settings
The following settings must be realised by a qualified person, trained to the product specifications.
Be careful, if you change the factory settings may lead to a malfunction.
GAS HEATER
SETTING
From the display « Gas heater setting», press 5 seconds on
« OK » to access to the different settings screens.
To change the display, press ▲
TEMPERATURE
FAN ON : 45 C
The display shows the temperature when fan starts. Press
« OK » and adjust the requested set point value with ▼ and ▲
and press « OK ». The factory setting value is 45 °C.
From 45 °C the axial fan starts and stops when the blowing
temperature will be lower to the setting –3°C (ON 45 °C / OFF 42
°C for factory settings).
To change the display, press ▲
TEMPORISATION
FAN ON : 60 SEC
The display shows the delay time when the fan starts. Press
« OK » and adjust the requested set point value with ▼ and ▲
and press « OK ». The factory setting value is 60 seconds. The
axial fan starts 60 seconds after the burner ignites and stops
when the burner stops except if the blowing temperature is over
the set value : Temperature FAN ON (previous setting).
To change the display, press ▲
TEMPERATURE
P. MAXI : 65 °C
The display shows the temperature at maximum power. Press
« OK » and adjust the requested set point value with ▼ et ▲
then validate with « OK ». The factory setting value is 65 °C. The
burner goes to Min P when the blowing temperature is over the
set value and in P. MAXI when the blowing temperature is lower
than the setting - 5 °C (P. MINI 65 °C / P. MAXI 60 °C for factory
settings).
To change the display, press ▲
EXHAUST FAN
START SPEED: 80
AIR PRESSURE
P; MAXI : 150 PA
AIR PRESSURE
P; MINI : 70 PA
To set up those displays, refer to the chapter « Burner combustion setting »