12
Airflow
Available pressure
Delta T
Motor power
dBa (LwoA)
8000
175
21
1800
87.0
7750
206
21
1700
86.7
7500
222
22
1600
85.8
7250
238
23
1500
85.0
7000
253
24
1420
84.7
6750
264
24
1340
84.0
6500
274
25
1275
83.5
6250
284
26
1220
82.7
6000
294
27
1140
82.1
5750
298
29
1070
81.6
ATX80C Heater
It is equipped with a belt driven centrifugal fans AT15-15 (transmission of 118/224) with three-phase
motor of 2200 W (Rotation : 745 rpm). The motor is connected to a frequency converter single-phase
230V IN and three-phase 230V OUT. The frequency converter allows the protection and the control of
motor speed to reach the requested performances.
Blowing unit performances:
Airflow
Available pressure
Delta T
Motor power
dBa (LwoA)
10500
180
20
2150
88.0
10000
209
21
1950
86.9
9500
228
23
1800
86.0
9000
247
24
1650
85.0
8500
264
25
1500
83.8
8000
277
27
1400
82.9
7500
289
29
1280
81.7
7000
296
31
1150
80.8
6500
302
33
1050
79.8
6000
307
36
900
79.0
2.4 Curves pressure/ariflow for ATXC
ATX60C Heater
It is equipped with a belt driven centrifugal fans AT12-12 (transmission of 112/170) with three-phase
motor of 1500 W (Rotation : 940 rpm). The motor is connected to a frequency converter single-phase
230V IN and three-phase 230V OUT. The frequency converter allows the protection and the control of
motor speed to reach the requested performances.
Caution: over 7 250 m3/h of airflow, the high airflow option with 2.2 kW frequency converter
should be provided. Please consult us.
Blowing unit performances: