3.6
LIGHTING THE APPLIANCE (All models)
a)
Turn on the gas isolation tap.
b)
Depress the control knob and turn anti-clockwise to the position
marked ignition / low rate. Hold in the control knob for a few seconds to
purge the pipe work.
c)
Continue to hold-in the control knob and press the igniter button. If the
burner does not light, continue to press the igniter button until ignition
occurs. Continue to hold the control knob for a minimum of 20 seconds
to allow the thermocouple to heat up, if the burner goes out when the
control knob is released, repeat the lighting sequence.
d)
Turn the control knob in the anti-clockwise direction to the high position
and the gas rate will increase to high rate (6.5 kW)
e)
Turn the control knob clockwise to the low position and the gas input
will be reduced to the minimum setting (2.2 kW)
f)
Slightly depress the control knob and turn to the off position, the burner
will now be extinguished.
WARNING : If the fire goes out for any reason or is turned off and it
is necessary to re-light the fire it is important to allow the
fire to cool for 3 minutes before attempting to re-light it.
3.7
CHECKING FOR CLEARANCE OF COMBUSTION PRODUCTS
a)
Close all doors and windows in the room.
b)
Light the fire and allow to run for approximately 5 minutes on high
position.
c)
After approximately 5 minutes hold a smoke match just inside and
below the centre of the lower front edge of the top of the fire. (It is
recommended that a suitable smoke match holder is used when check
ing for clearance of combustion products). All smoke generated should
be drawn back into the flue. If slight spillage occurs or if in doubt,
repeat the test after a further 5-10 minutes.
If the test indicates that
spillage is occurring and the flue restrictor baffle has been fitted, it
should be removed and the test repeated after the fire has cooled.
d)
If spillage persists, the flue is not functioning correctly and a fault exists.
If, after investigation the fault cannot be traced and rectified, the fire
must be disconnected from the gas supply and expert advice obtained.