2.7
(CONTINUED) FITTING THE TERMINAL GUARD
2.7.5
With the flue terminal in position, place the terminal guard over the top
of the flue terminal and mark the position of the holes on the outer wall.
2.7.6
Remove the terminal guard and drill the 4 off 6 mm holes.
2.7.7
Insert the raw plugs into the drilled holes, replace the terminal guard
over the top of the flue terminal and attach to the wall using the No.12 x
40mm screws provided with the terminal guard.
NOTE :
In England & Wales, building regulations require that a terminal guard should be
fitted if the terminal could come into contact with people near the building or be
subject to damage. BFM Europe Ltd. also recommend the fitting of a flue terminal
guard where regulations do not demand that it be fitted. A suitable flue terminal
guard is supplied with the appliance.
2.8
MAKING THE GAS CONNECTION / PRESSURE TESTING
THIS APPLIANCE IS INTENDED FOR USE ON A GAS SUPPLY WITH
A GOVERNED METER.
2.8.1
The gas connection should be made to the appliance inlet elbow to
using 8mm rigid tubing.
2.8.2
Remove the pressure test point screw from the inlet elbow and fit a
manometer.
2.8.3
Fit the batteries as per section 2.9, turn on the main gas supply and
carry out a gas tightness test. Light the fire (see section 3.2 for
instructions).
2.8.4
Check that the gas pressure is
20.0 mbar (+/- 1.0mbar) 8.0 in w.g.(+/-
0.4 in w.g.).
Turn off the stove, remove the manometer and refit the
pressure test point screw. Check the pressure test point screw for gas
tightness with the appliance turned on using a suitable leak detection
fluid or detector.
12