Flavel Atlanta FBFR MN Series Installation And Maintenance Instructions Manual Download Page 22

 

22 

SECTION 3 

MAINTENANCE 

 

Servicing Notes 

 

 

Servicing should be carried out annually by a competent person such as a GAS 
SAFE registered engineer.  It is a condition of Flavel guarantees that this is carried 
out by a competent person  a GAS SAFE registered Engineer in accordance with 
these servicing notes 

  For continued safe operation of the fire the pilot assembly must be replaced at the 

annual service.  Pilot renewal is also a condition of the above guarantee schemes. 

  The condition of the Fibre ribbed back should be checked and 

if necessary should be 

replaced with a genuine replacement only available from BFM Europe Ltd.

 

 

 
3.1 

Removing the Piezo Igniter. 

 

a)   Remove fascia from the front of the fire. 

Isolate the gas supply, loosen the inlet nut, and remove the 2 screws that secure the 
pilot heat shield, remove the shield. 

b)   Loosen the nut to the bulkhead fitting, which is located to the left-hand side of the 
 

convection air aperture. 

c)   Loosen the pilot pipe, disconnect the ignition lead from the electrode and disconnect 
  

the thermocouple from the pilot assembly. 

d)   Remove the 4 off fixing screws that secure the control panel in place. 
e)   Slide the control panel and gas train forwards. 
f)    Disconnect the ignition lead from the piezo and unscrew the retaining nut on the rear of 
  

the control panel.  Withdraw the piezo from the front of the control panel.  Reassemble 

  

in reverse order and carry out a gas tightness test. 

 

3.2 

Removing the Control Valve from the fire. 

 

a)     Remove the fascia from the front of the fire to a safe location. 
b)     Isolate the gas supply. Loosen the inlet nut, remove the 2 screws that secure the pilot 
 

heat shield, remove the shield. 

c)     Unscrew the pilot heat shield and remove from the fire. 
d)     Loosen the nut to the bulkhead fitting, which is located to the L/H/S of the convection 
 

air aperture. 

 

e)     Unscrew the 4 screws that secure the control panel in place. 
f)      Loosen and remove the pilot pipe, ignition lead and thermocouple from the pilot body. 

 

g)     Pull the control panel away from the fire. 
h)     Pull the control knob from the valve and remove the control valve-locking nut. 
i)       Unscrew the inlet nut, pilot nut, main pipe and release the thermocouple nut from the 
  

end of the control valve. We do not recommend re-greasing or servicing of control 

 

valves. Defective valves should be replaced with a genuine replacement of the correct 

 

type. 

j)       To refit a control tap, reassemble in reverse order noting that the control tap locates 
  

with a flat in the control panel.  Carry out a gas tightness test after reassembly. 

 
 
 

Summary of Contents for Atlanta FBFR MN Series

Page 1: ...allation and Maintenance Instructions Hand these instructions to the user This appliance is only for use on Natural Gas G20 at a supply pressure of 20 mbar in GB I E Before Installation ensure that th...

Page 2: ...Heat Output 66 4 Useful Efficiency at Minimum Heat Output Indicative 50 0 Auxilliary Power Consumption at Nominal Heat Output Not applicable Auxilliary Power Consumption at Minimum Output Not applica...

Page 3: ...er pressure 19 20 2 11 Lighting the appliance 20 Section 3 Maintenance 3 1 Removal of the Piezo Igniter 21 3 2 Removal of the Control valve 21 3 3 Removal of the Pilot Assembly 22 3 4 Removal of the b...

Page 4: ...2 5 kW Cold Pressure 20 0 1 0 mbar 8 0 0 4 in w g Ignition Push button Piezo Electrode Spark Gap 4 0mm Weight without fender 26 0 kg inclusive of flue pipe and terminal Before installation ensure tha...

Page 5: ...tment and all applicable requirements of the following British Standard Code of Practice 1 B S 5871 Part 1 Installation of Gas Fires 2 B S 6891 Installation of Gas Pipework 3 B S 5440 Parts 1 2 Instal...

Page 6: ...B Below gutters soil pipes or drain pipes 75mm C Below eaves 200mm D Below balconies or car port roof 200mm E From a vertical drain pipe or soil pipe 75mm F From an internal or external corner 300mm G...

Page 7: ...erhangs more than 150mm the distance between the fire and the shelf must be increased by 15mm for every 25mm of additional overhang over 150mm 1 5 HEARTHS This appliance does not require the fitting o...

Page 8: ...mbly Ashpan Cover 1off Flue Terminal unit pack 2 of 2 1off Loose Items pack containing 1 off Flue pipe gasket 4 off No 12 x 65mm fixing screws 15 off No 8 x 10mm fixing screws 4 off rawplugs 1 off 6mm...

Page 9: ...itted into a fireplace fire surround or false chimney constructed of non combustible materials minimum width 402mm minimum rebate 50mm with optional black 3 spacer fitted or 125mm without black spacer...

Page 10: ...of the flue on both the inner and outer walls 2 3 2 Mark the positions of the cable fixing eyes See p15 fig 11 2 3 3 Cut hole for outer flue pipe There are two possible methods to achieve this either...

Page 11: ...d correctly secured in the final position From the outside of the house measure from the face of the outside wall to the rear panel of the firebox through the flue hole This dimension is shown below a...

Page 12: ...or sealing compound seal the outer flue pipe to the outside surface of the wall See sketch on the page 11 for position of mortar Fig 7 NOTE 12 Screws are provided six off to affix the inner flue pipe...

Page 13: ...des of the firebox and connect to the inlet elbow See fig 8 below for a suggested concealed pipe layout Fig 8 Without optional 3 black spacer Note Before breaking into the gas supply a tightness test...

Page 14: ...lush fit spacer option is used the fire may be secured using the cable method as described on page 16 or alternatively in installations where the cable method is not suitable e g loose masonary in rea...

Page 15: ...4 off wall plugs provided into these holes move the firebox up to the wall inserting the flue pipe into the hole then secure to the wall using the 4 off No 10 x screws provided See fig 10 below i Usin...

Page 16: ...eye in the centre of the wall Thread the free end of the cables through the circular hole on lower centre rear of the fire Carefully slide the firebox back into the fire opening whilst threading both...

Page 17: ...r of the access holes in the sides of the fire the holes should be closed around the pipe to prevent leakage of air through the gap around the pipe o Before making the final gas connection thoroughly...

Page 18: ...y provided remove the 4 allen key screws c Refit the glass frame in reverse order from above Remove the cardboard packaging that secures the blast flap and press down on the blast flap to secure the s...

Page 19: ...ar the building or are subject to damage BFM Europe Ltd also recommend the fitting of a flue terminal guard where regulations do not demand that it be fitted 2 9 FITTING THE OPTIONAL TERMINAL GUARD Wi...

Page 20: ...he control knob for a few seconds to purge the pipe work then press the igniter button The burner should light continue to hold the control knob for a few seconds then turn to the full on position d C...

Page 21: ...knob clockwise to the low position and the gas input will be reduced to the minimum setting f Slightly depress the control knob and turn to the pilot position the main burner will go out but the pilo...

Page 22: ...panel and gas train forwards f Disconnect the ignition lead from the piezo and unscrew the retaining nut on the rear of the control panel Withdraw the piezo from the front of the control panel Reasse...

Page 23: ...a safe location b Remove the glass frame as described in section 3 2 c Isolate the gas supply d Unscrew the 2 screws that secure the pilot heat shield in place e Unscrew the 2 screws that secure the...

Page 24: ...t the exact accuracy of illustrations and descriptions contained in this book cannot be guarantee Part B 1004452 Issue 1 BFM Europe Ltd Trentham Lakes Stoke on Trent Staffordshire ST4 4TJ www bfm euro...

Reviews: