FLAMCO-FILL PE INSTALLATION AND OPERATING INSTRUCTIONS
TP.04/02/09.EN
Edition 2009 / EXP
9
Technical specifications
H2
W2
W1
D2
D1
General
Type of protection
IP 54
Weight
ca. 25 kg
System installation
G ½”
Feed joint at the impulse water counter
R ½”
Pipe joint drain/overflow
DN40
Volume system separation box
12 litre
System data
Supply flow pressure
1 – 10 bar
System pressure
1 – 9 bar
Volume flow
max. 210 l/h
Temperature range supply
> 0 °C – 30 °C
Electrical data
Supply voltage
230 V, 50 Hz
Power input
0,3 kW
Mains fuse
230 V, 10 A (slow)
Load capacity collective malfunction message
230 VAC, 3 A
Influencing variables
Environmental temperature
> 0 °C – 40 °C during operation, -20 °C – 65 °C when transported and stored.
Relative humidity
< 80% during operation, when transported and stored -> non-condensing.
Main dimensions (nominal)
H2
495 mm
W1
380 mm
W2
320 mm
D1
320 mm
D2
215 mm
Nominal diameter
Maximum line length system installation
DN15
10 m
DN20
20 m
DN25
30 m