EU Air Handling Unit

MAINTENANCE

EUQA Humidifier, for circulated water

To set the timer for emptying and flushing

For normal function, the timer should be preset  to
"ON". When emptying, which can be programmed to
occur once or several (optional) times every 24-hour peri-
od, the timer will reset itself to the "OFF" setting for 10
minutes. After that, the timer will reset itself to "ON" for
2 minutes to allow flushing.

The timer will then reset itself to the "OFF" setting for

3 minutes  for additional emptying before resetting itself
back to "ON" for normal operation. 

In the following example, emptying and flushing are

required once every 24 hours from 12.00 to 12.15 as
scheduled below.

Periods

Timer setting

Activity

00.00–12.00

ON

Normal operation

12.00–12.10

OFF

Emptying

12.10–12.12

ON

Flushing

12.12–12.15

OFF

Additional emptying

12.15–24.00

ON

Normal operation

This can be done most easily by programming the opera-
tion times from 12.15 to 12.00 and from 12.10 to 12.12
on a daily basis! Emptying and additional emptying will
then occur from 12.00 to 12.10 and from 12.12 to 12.15
respectively.

Water quality

Evaporation causes an increase in the concentration of
minerals in the circulating water, which necessitates
continuous bleed-off and make-up with fresh water.
The bleed-off rate is dependent on factors such as:

the pH of the water

the bicarbonate concentration (HCO

3

), mg/l

the calcium concentration (Ca

2+

), mg/l

This data can be obtained from a municipal water autho-
rity or by analysing the water.
Lime precipitation can be prevented by plotting the per-
tinent data in Chart 1 on page 4 to determine the current
risk zone. Water level monitor B can then be set accor-
ding to the relevant zone. If the water is too hard, it may
be necessary to subject it to partial softening.
In addition to the risk of lime precipitation, the concent-
ration of chlorine (Cl) and copper (Cu) must be taken
into account. To ensure acceptable performance, the con-
centration of Cl in the fresh water must not exceed 50
mg/l and that of Cu must not exceed 0.02 mg/l.

Summary of Contents for EUQA

Page 1: ...assified If the water is of zone 4 type it should be softened Level monitors fig 2 Level monitor A Closes the water supply valve when the water reaches max level A Setting A 25 mm from the upper edge of the water tray sizes 20 53 65 mm from the upper edge of the water tray sizes 60 84 Level monitor B Opens the drain valve for water bleed off Setting B The zone value obtained see page 5 determines ...

Page 2: ...pening the drain valve approx half way 45 see Fig 3 The valve can be reclosed by pressing a reset button on the control unit When the water level has dropped below the lowest point of sensor B the drain valve should open fully If the water level continues to drop below the lowest point of sensor C water inlet valve should begin to open and after a preset period see Table 2 Fig 6 the drain valve sh...

Page 3: ...5 12 M A1 15 B1 A2 18 16 Rel Power TR1 Fig 6 Table 3 Presetting time relay TR1 Seconds Range Time 0 1 s 0 10 10 s 10 red 20 30 s 20 black 30 30 s 30 black 40 100 s 4 red 50 100 s 5 red 60 100 s 6 red 70 100 s 7 red 80 100 s 8 red 90 100 s 9 red 100 100 s 10 red 120 300 s 12 black 180 300 s 18 black 240 300 s 24 black 300 300 s 30 black Q1 K1 R1 NR3 NR2 NR1 TR1 Fig 7 Components inside the control b...

Page 4: ...ost easily by programming the opera tion times from 12 15 to 12 00 and from 12 10 to 12 12 on a daily basis Emptying and additional emptying will then occur from 12 00 to 12 10 and from 12 12 to 12 15 respectively Water quality Evaporation causes an increase in the concentration of minerals in the circulating water which necessitates continuous bleed off and make up with fresh water The bleed off ...

Page 5: ... the time zone where it is to be used Display of special functions Manual operation Permanent ON OFF Symbols which indicate summer winter function Summer Winter The numbers under the display indicate days of the week 1 Monday 2 Tuesday etc Choice Yes means choice of programming Choice No means continue Day by day summary of the programmed connection times Example 5 Friday Duct status ON On OFF OFF...

Page 6: ... If the concentration of salts is too high salts may be deposited on the humidifier fill which will have a detrimental effect on the performance of the humidifier The chart above can be used to determine the appropria te bleed off flow If the humidifier has been sized for running over a long period at a high humidification rate x above 8 grams per kg of air 90 humidifier and x above 5 grams per kg...

Page 7: ...tom of the water tray E The fills are relatively delicate and should therefore be treated with great care Clean by spraying with a jet of clean water possibly containing some ULCZ 01 clea ning agent When replacing the humidifier fills see the appropriate instructions supplied with the new fills F Refit the components in the reverse order G Check the position of the side wall and close the inspecti...

Page 8: ...operation when the tray is dry NR2 A B3 B2 16 B1 A1 A2 17 A2 A1 B1 B2 B3 B NR3 Maintains correct level 4 B1 A2 A1 TR1 Delayed closure SV1 TR1 15 16 18 R1 11 12 14 R1 21 22 24 R1 31 32 34 1 2 3 4 5 G G 7 8 6 Control box on outside Control box on inside 1 3 5 2 4 6 W U V 3 M 6 4 2 3 5 1 I I I K2 A1 A2 Contactor CP2 Humidity control Interlock Wiring diagram Service intervals Component Service work In...

Reviews: