EUQA Humidifier, for circulated water

Fläkt Woods

3176 GB 05.08

3

Specifications are subject to alteration without notice

EU Air Handling Unit

MAINTENANCE

Table 2. Presetting the time relay

Time relay TR1 has been preset for
normal operation. If the time
required for emptying has to be
increased due to humidification
over a long period, this can be
done as follows:
1. Select Function 12
2. Select the Range
3. Select Time

– If Range has red digits, Time

shows tenths of Range

– If Range has black digits,

Time shows thirtieths of
Range.

Example: To set a time of 240 sec.

– Select a Range of 300

sec. (black digits)

– Select a Time of 24

(black digits)

Range

Time

ETR4–69–A

Function

1s

1.5 .5

12

M

A1~+

15

B1

A2~-

18

16

Rel

Power

TR1

Fig. 6

Table 3. Presetting time relay TR1

Seconds

Range

Time

0

1  s

0

10

10 s

10 red

20

30 s

20 black

30

30 s

30 black

40 100 

s

red

50

100 s

5 red

60

100 s

6 red

70

100 s

7 red

80

100 s

8 red

90

100 s

9 red

100

100 s

10 red

120

300 s

12 black

180

300 s

18 black

240

300 s

24 black

300

300 s

30 black

Q1

K1

R1

NR3

NR2

NR1

TR1

Fig. 7

Components inside the control box

Time required for emptying

Normal operation

High humidification

Size

preset value

over a long period

x >8 gram

x >5 gram

90%

60%

90%

60%

20

0

0

0

0

21

10

0

20

0

22

20

0

30

10

30

10

0

20

0

31

10

0

20

0

32

20

0

40

10

33

30

0

60

20

40

30

0

90

20

41

30

0

80

20

42

50

0

100

30

44

60

0

120

40

50

40

0

80

30

51

70

0

120

50

52

55

0

55

20

53

60

0

60

20

60

30

0

30

0

62

60

0

90

0

64

60

30

240

120

71

60

30

180

90

73

90

60

240

120

80

90

60

180

120

82

90

60

240

120

84

120

60

300

120

Summary of Contents for EUQA

Page 1: ...assified If the water is of zone 4 type it should be softened Level monitors fig 2 Level monitor A Closes the water supply valve when the water reaches max level A Setting A 25 mm from the upper edge of the water tray sizes 20 53 65 mm from the upper edge of the water tray sizes 60 84 Level monitor B Opens the drain valve for water bleed off Setting B The zone value obtained see page 5 determines ...

Page 2: ...pening the drain valve approx half way 45 see Fig 3 The valve can be reclosed by pressing a reset button on the control unit When the water level has dropped below the lowest point of sensor B the drain valve should open fully If the water level continues to drop below the lowest point of sensor C water inlet valve should begin to open and after a preset period see Table 2 Fig 6 the drain valve sh...

Page 3: ...5 12 M A1 15 B1 A2 18 16 Rel Power TR1 Fig 6 Table 3 Presetting time relay TR1 Seconds Range Time 0 1 s 0 10 10 s 10 red 20 30 s 20 black 30 30 s 30 black 40 100 s 4 red 50 100 s 5 red 60 100 s 6 red 70 100 s 7 red 80 100 s 8 red 90 100 s 9 red 100 100 s 10 red 120 300 s 12 black 180 300 s 18 black 240 300 s 24 black 300 300 s 30 black Q1 K1 R1 NR3 NR2 NR1 TR1 Fig 7 Components inside the control b...

Page 4: ...ost easily by programming the opera tion times from 12 15 to 12 00 and from 12 10 to 12 12 on a daily basis Emptying and additional emptying will then occur from 12 00 to 12 10 and from 12 12 to 12 15 respectively Water quality Evaporation causes an increase in the concentration of minerals in the circulating water which necessitates continuous bleed off and make up with fresh water The bleed off ...

Page 5: ... the time zone where it is to be used Display of special functions Manual operation Permanent ON OFF Symbols which indicate summer winter function Summer Winter The numbers under the display indicate days of the week 1 Monday 2 Tuesday etc Choice Yes means choice of programming Choice No means continue Day by day summary of the programmed connection times Example 5 Friday Duct status ON On OFF OFF...

Page 6: ... If the concentration of salts is too high salts may be deposited on the humidifier fill which will have a detrimental effect on the performance of the humidifier The chart above can be used to determine the appropria te bleed off flow If the humidifier has been sized for running over a long period at a high humidification rate x above 8 grams per kg of air 90 humidifier and x above 5 grams per kg...

Page 7: ...tom of the water tray E The fills are relatively delicate and should therefore be treated with great care Clean by spraying with a jet of clean water possibly containing some ULCZ 01 clea ning agent When replacing the humidifier fills see the appropriate instructions supplied with the new fills F Refit the components in the reverse order G Check the position of the side wall and close the inspecti...

Page 8: ...operation when the tray is dry NR2 A B3 B2 16 B1 A1 A2 17 A2 A1 B1 B2 B3 B NR3 Maintains correct level 4 B1 A2 A1 TR1 Delayed closure SV1 TR1 15 16 18 R1 11 12 14 R1 21 22 24 R1 31 32 34 1 2 3 4 5 G G 7 8 6 Control box on outside Control box on inside 1 3 5 2 4 6 W U V 3 M 6 4 2 3 5 1 I I I K2 A1 A2 Contactor CP2 Humidity control Interlock Wiring diagram Service intervals Component Service work In...

Reviews: