background image

EUQA Humidifier, for circulated water

Fläkt Woods

3176 GB 05.08

2

Specifications are subject to alteration without notice

EU Air Handling Unit

MAINTENANCE

Maintenance adjustments (Contd.)

The humidifier function:
– switch on the power supply to the humidifier. The

water tray will start to fill with water.

Check:
– that the pump has started and that it is pumping

water.

If there is no water flow, change the direction of rota-
tion of the pump, see Fig. 5. 
– preset the required supply water flow rate according

to Table 1. This is done by setting the adjustment
screw on the flow controller, shown in Fig. 4.

– that water is being discharged from all of the holes

in the spray pipe(s). If any holes are clogged, use a
needle to unclog them. If the spray pipe(s) is/are
extremely clogged, remove the end plugs (17), brush
inside them using a round brush and then flush
them clean.

– that the flow of supply water stops when the water

level in the tray reaches level monitor A.

– that water bleed-off can be done by manually opening

the drain valve approx. half way (45°), see Fig. 3.  The
valve can be reclosed by pressing a reset button on the
control unit. When the water level has dropped below
the lowest point of sensor B, the drain valve should
open fully. If the water level continues to drop below
the lowest point of sensor C, water inlet valve should
begin to open and after a preset period (see Table 2,
Fig. 6) the drain valve should start to close. When the
water reaches level C, the pump should soon stop.
(The pump should not run when the water level is
below level C.)

– The preset period on the time relay should be accor-

ding to Table 2, 3 and Fig. 6.

Droplet eliminator
The droplet eliminator fills must be correctly fitted for
the direction of air flow, see the arrow on the droplet
eliminator.

45°

45°

0

0

2

4

2

4

6

30

20

10

Fig. 3

Fig. 5

Table 1. Supply air flow

Water flow (l/min)

Adjusting screw

Fig. 4

Reset button

Size        Supply water flow, l/min

Aluminium

90%

60%

20

10.0

5.0

21

15.0

7.5

22

20.0

10.0

30

15.0

7.5

31

20.0

10.0

32

25.0

12.5

33

30.0

15.0

40

20.0

10.0

41

25.0

12.5

42

30.0

15.0

44

40.0

20.0

50

25.0

12.5

51

30.0

15.0

52

35.0

17.5

53

40.0

20.0

60

30

15

62

40

20

64

50

25

71

40

20

73

50

25

80

40

20

82

50

25

84

60

30

Summary of Contents for EUQA

Page 1: ...assified If the water is of zone 4 type it should be softened Level monitors fig 2 Level monitor A Closes the water supply valve when the water reaches max level A Setting A 25 mm from the upper edge of the water tray sizes 20 53 65 mm from the upper edge of the water tray sizes 60 84 Level monitor B Opens the drain valve for water bleed off Setting B The zone value obtained see page 5 determines ...

Page 2: ...pening the drain valve approx half way 45 see Fig 3 The valve can be reclosed by pressing a reset button on the control unit When the water level has dropped below the lowest point of sensor B the drain valve should open fully If the water level continues to drop below the lowest point of sensor C water inlet valve should begin to open and after a preset period see Table 2 Fig 6 the drain valve sh...

Page 3: ...5 12 M A1 15 B1 A2 18 16 Rel Power TR1 Fig 6 Table 3 Presetting time relay TR1 Seconds Range Time 0 1 s 0 10 10 s 10 red 20 30 s 20 black 30 30 s 30 black 40 100 s 4 red 50 100 s 5 red 60 100 s 6 red 70 100 s 7 red 80 100 s 8 red 90 100 s 9 red 100 100 s 10 red 120 300 s 12 black 180 300 s 18 black 240 300 s 24 black 300 300 s 30 black Q1 K1 R1 NR3 NR2 NR1 TR1 Fig 7 Components inside the control b...

Page 4: ...ost easily by programming the opera tion times from 12 15 to 12 00 and from 12 10 to 12 12 on a daily basis Emptying and additional emptying will then occur from 12 00 to 12 10 and from 12 12 to 12 15 respectively Water quality Evaporation causes an increase in the concentration of minerals in the circulating water which necessitates continuous bleed off and make up with fresh water The bleed off ...

Page 5: ... the time zone where it is to be used Display of special functions Manual operation Permanent ON OFF Symbols which indicate summer winter function Summer Winter The numbers under the display indicate days of the week 1 Monday 2 Tuesday etc Choice Yes means choice of programming Choice No means continue Day by day summary of the programmed connection times Example 5 Friday Duct status ON On OFF OFF...

Page 6: ... If the concentration of salts is too high salts may be deposited on the humidifier fill which will have a detrimental effect on the performance of the humidifier The chart above can be used to determine the appropria te bleed off flow If the humidifier has been sized for running over a long period at a high humidification rate x above 8 grams per kg of air 90 humidifier and x above 5 grams per kg...

Page 7: ...tom of the water tray E The fills are relatively delicate and should therefore be treated with great care Clean by spraying with a jet of clean water possibly containing some ULCZ 01 clea ning agent When replacing the humidifier fills see the appropriate instructions supplied with the new fills F Refit the components in the reverse order G Check the position of the side wall and close the inspecti...

Page 8: ...operation when the tray is dry NR2 A B3 B2 16 B1 A1 A2 17 A2 A1 B1 B2 B3 B NR3 Maintains correct level 4 B1 A2 A1 TR1 Delayed closure SV1 TR1 15 16 18 R1 11 12 14 R1 21 22 24 R1 31 32 34 1 2 3 4 5 G G 7 8 6 Control box on outside Control box on inside 1 3 5 2 4 6 W U V 3 M 6 4 2 3 5 1 I I I K2 A1 A2 Contactor CP2 Humidity control Interlock Wiring diagram Service intervals Component Service work In...

Reviews: